4 AWG Wire Size

AWG Wire Gauge

4 AWG solid wire is 0.2043 in (5.189 mm) in diameter, with a copper cross-section of 21.15 mm² (41,740 circular mils). Solid annealed copper of this size has a DC resistance of 0.8152 Ω/km (0.2485 Ω/1000 ft) at 20 °C.

dDiameter
5.189 mm0.2043 in0.2043 in5.189 mm
ACross-section
21.15 mm²
RDC resistance, copper 20 °C
0.8152 Ω/km
Ampacity 75 °C (NEC)
85 A

Drawing

⌀5.189 mm⌀0.2043 inSolid21.15 mm²
⌀5.884 mm⌀0.2317 in7 × ⌀1.961 mm⌀0.0772 in7 strands, same area
Bare conductor without insulation; 7-strand shown as an uncompressed concentric lay.Drawn to scale · Dimensions in mmDimensions in inches

4 AWG specifications

dDiameter0.2043 in5.189 mm
ACross-section21.15 mm²
Circular mils41,740
RDC resistance, copper 20 °C0.8152 Ω/km
RDC resistance, copper 20 °C0.2485 Ω/1000 ft
Ampacity 60 °C (NEC)70 A
Ampacity 75 °C (NEC)85 A
Ampacity 90 °C (NEC)95 A
Next metric size up25 mm²

4 AWG is a common size for 85 A feeders (75 °C), welding cable for small machines and battery cables in vehicles and boats.

Also known as

#4

Metric (IEC 60228) size with at least the same area

All AWG Wire Gauge sizes

Compare all 44 sizes in the AWG Wire Gauge chart →

Sources

  1. ASTM B258: Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors
  2. NFPA 70, National Electrical Code (2023), Table 310.16: Ampacities of insulated conductors, 60/75/90 °C
  3. IEC 60028:1925, International standard of resistance for copper (annealed copper: 1/58 Ω·mm²/m at 20 °C)
  4. IEC 60228:2023, Conductors of insulated cables (metric nominal cross-sections)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.