AWG Wire Gauge Chart
American Wire Gauge sizes from 4/0 down to 40 AWG, calculated from the ASTM B258 formula. Rule of thumb: every 3 gauges halve the copper area and double the resistance. 12 AWG has twice the area of 15 AWG and half that of 9 AWG.
Size chartTap a size for its drawing and full specs
| Gauge | dDiametermmin | ACross-sectionmm² | Circular mils | RDC resistance, copper 20 °CΩ/km | RDC resistance, copper 20 °CΩ/1000 ft | Ampacity 60 °C (NEC)A | Ampacity 75 °C (NEC)A | Ampacity 90 °C (NEC)A | Next metric size up |
|---|---|---|---|---|---|---|---|---|---|
| 4/0 AWG | 11.6840.4600 | 107.2 | 211,600 | 0.1608 | 0.049 | 195 | 230 | 260 | 120 mm² |
| 3/0 AWG | 10.4040.4096 | 85.03 | 167,800 | 0.2028 | 0.0618 | 165 | 200 | 225 | 95 mm² |
| 2/0 AWG | 9.2660.3648 | 67.43 | 133,100 | 0.2557 | 0.0779 | 145 | 175 | 195 | 70 mm² |
| 1/0 AWG | 8.2520.3249 | 53.48 | 105,500 | 0.3224 | 0.0983 | 125 | 150 | 170 | 70 mm² |
| 1 AWG | 7.3480.2893 | 42.41 | 83,690 | 0.4066 | 0.1239 | 110 | 130 | 145 | 50 mm² |
| 2 AWG | 6.5430.2576 | 33.63 | 66,370 | 0.5127 | 0.1563 | 95 | 115 | 130 | 35 mm² |
| 3 AWG | 5.8270.2294 | 26.67 | 52,630 | 0.6464 | 0.197 | 85 | 100 | 115 | 35 mm² |
| 4 AWG | 5.1890.2043 | 21.15 | 41,740 | 0.8152 | 0.2485 | 70 | 85 | 95 | 25 mm² |
| 5 AWG | 4.6200.1819 | 16.77 | 33,100 | 1.028 | 0.3133 | — | — | — | 25 mm² |
| 6 AWG | 4.1150.1620 | 13.3 | 26,250 | 1.296 | 0.3951 | 55 | 65 | 75 | 16 mm² |
| 7 AWG | 3.6650.1443 | 10.55 | 20,820 | 1.634 | 0.4982 | — | — | — | 16 mm² |
| 8 AWG | 3.2640.1285 | 8.366 | 16,510 | 2.061 | 0.6282 | 40 | 50 | 55 | 10 mm² |
| 9 AWG | 2.9060.1144 | 6.634 | 13,090 | 2.599 | 0.7921 | — | — | — | 10 mm² |
| 10 AWG | 2.5880.1019 | 5.261 | 10,380 | 3.277 | 0.9988 | 30 | 35 | 40 | 6 mm² |
| 11 AWG | 2.3040.0907 | 4.172 | 8,234 | 4.132 | 1.26 | — | — | — | 6 mm² |
| 12 AWG | 2.0520.0808 | 3.309 | 6,530 | 5.211 | 1.588 | 20 | 25 | 30 | 4 mm² |
| 13 AWG | 1.8290.0720 | 2.624 | 5,178 | 6.571 | 2.003 | — | — | — | 4 mm² |
| 14 AWG | 1.6280.0641 | 2.081 | 4,107 | 8.285 | 2.525 | 15 | 20 | 25 | 2.5 mm² |
| 15 AWG | 1.4500.0571 | 1.65 | 3,257 | 10.45 | 3.184 | — | — | — | 2.5 mm² |
| 16 AWG | 1.2900.0508 | 1.309 | 2,583 | 13.17 | 4.015 | — | — | — | 1.5 mm² |
| 17 AWG | 1.1510.0453 | 1.038 | 2,048 | 16.61 | 5.063 | — | — | — | 1.5 mm² |
| 18 AWG | 1.0240.0403 | 0.823 | 1,624 | 20.95 | 6.385 | — | — | — | 1 mm² |
| 19 AWG | 0.9120.0359 | 0.6527 | 1,288 | 26.41 | 8.051 | — | — | — | 0.75 mm² |
| 20 AWG | 0.8130.0320 | 0.5176 | 1,022 | 33.31 | 10.15 | — | — | — | 0.75 mm² |
| 21 AWG | 0.7240.0285 | 0.4105 | 810.1 | 42 | 12.8 | — | — | — | — |
| 22 AWG | 0.6430.0253 | 0.3255 | 642.4 | 52.96 | 16.14 | — | — | — | — |
| 23 AWG | 0.5740.0226 | 0.2582 | 509.5 | 66.78 | 20.36 | — | — | — | — |
| 24 AWG | 0.5110.0201 | 0.2047 | 404 | 84.21 | 25.67 | — | — | — | — |
| 25 AWG | 0.4550.0179 | 0.1624 | 320.4 | 106.2 | 32.37 | — | — | — | — |
| 26 AWG | 0.4040.0159 | 0.1288 | 254.1 | 133.9 | 40.81 | — | — | — | — |
| 27 AWG | 0.3610.0142 | 0.1021 | 201.5 | 168.9 | 51.47 | — | — | — | — |
| 28 AWG | 0.3200.0126 | 0.081 | 159.8 | 212.9 | 64.9 | — | — | — | — |
| 29 AWG | 0.2870.0113 | 0.0642 | 126.7 | 268.5 | 81.83 | — | — | — | — |
| 30 AWG | 0.2540.0100 | 0.0509 | 100.5 | 338.5 | 103.2 | — | — | — | — |
| 31 AWG | 0.2260.0089 | 0.0404 | 79.7 | 426.9 | 130.1 | — | — | — | — |
| 32 AWG | 0.2030.0080 | 0.032 | 63.21 | 538.3 | 164.1 | — | — | — | — |
| 33 AWG | 0.1800.0071 | 0.0254 | 50.13 | 678.8 | 206.9 | — | — | — | — |
| 34 AWG | 0.1600.0063 | 0.0201 | 39.75 | 856 | 260.9 | — | — | — | — |
| 35 AWG | 0.1420.0056 | 0.016 | 31.52 | 1079 | 329 | — | — | — | — |
| 36 AWG | 0.1270.0050 | 0.0127 | 25 | 1361 | 414.8 | — | — | — | — |
| 37 AWG | 0.1140.0045 | 0.0101 | 19.83 | 1716 | 523.1 | — | — | — | — |
| 38 AWG | 0.1020.0040 | 0.008 | 15.72 | 2164 | 659.6 | — | — | — | — |
| 39 AWG | 0.0890.0035 | 0.0063 | 12.47 | 2729 | 831.8 | — | — | — | — |
| 40 AWG | 0.0790.0031 | 0.005 | 9.89 | 3441 | 1049 | — | — | — | — |
No exact match. The nearest sizes:
How the gauge numbers work
AWG is a geometric series defined in ASTM B258. Gauge 36 is exactly 0.005 in and gauge 0000 (4/0) is exactly 0.4600 in; the 38 steps between them share one ratio, so the diameter of gauge n is d = 0.005 in × 92^((36 − n)/39). Each gauge step changes the diameter by a factor of about 1.1229 and the area by about 1.261.
Useful consequences: 3 gauges = half or double the area (and resistance), 6 gauges = half or double the diameter, and 10 gauges = ten times the area. A smaller number means a thicker wire. Sizes above 1 AWG are written 1/0, 2/0, 3/0, 4/0 (spoken "one-aught" to "four-aught") or 0, 00, 000, 0000. Beyond 4/0, North American cable is sized in kcmil (thousands of circular mils): 250 kcmil, 500 kcmil and so on.
A circular mil is the area of a circle 0.001 in (one mil) in diameter, so the area in circular mils is simply the diameter in mils squared: 12 AWG is 80.8 mil, 80.8² ≈ 6530 cmil. To convert to mm², multiply circular mils by 0.000 506 7.
The diameters are for solid round wire. Stranded wire of the same gauge has the same copper area but is 10–15 % larger over the strands (see the drawing on each size page). To identify an unknown wire, strip it and measure the bare solid conductor with a caliper or micrometer; for stranded wire, count and measure one strand and compare the total area.
About AWG Wire Gauge
The table lists every AWG size from 4/0 to 40, calculated from the ASTM B258 formula. Areas are given in mm² and circular mils; resistance is for solid annealed copper at 20 °C, using the international annealed copper standard of 1/58 Ω·mm²/m (1.7241 × 10⁻⁸ Ω·m). Stranded and tinned conductors are a few per cent higher, and resistance rises about 0.39 % per °C, so a conductor at 75 °C has roughly 22 % more resistance than the table shows.
Ampacity values are from NEC Table 310.16 for copper conductors: 30 °C ambient, not more than three current-carrying conductors in a raceway, cable or earth. The three columns belong to the conductor temperature rating: 60 °C for UF cable (and the ampacity limit of NM cable, NEC 334.80), 75 °C for THW and THWN, 90 °C for THHN, THWN-2 and XHHW-2. In practice the terminations usually limit you to the 60 °C or 75 °C column (NEC 110.14(C)), and the 90 °C value is only the starting point for derating.
Small conductors have a separate overcurrent limit: NEC 240.4(D) allows at most 15 A on 14 AWG, 20 A on 12 AWG and 30 A on 10 AWG copper, regardless of the higher table ampacity. That is why a 20 A household circuit needs 12 AWG.
For metric cable, the last column gives the smallest IEC 60228 nominal size with at least the same copper area, which is the safe direction when replacing an AWG conductor with a metric one. Metric sizes are not exact equivalents: 2.5 mm² sits between 14 AWG (2.08 mm²) and 12 AWG (3.31 mm²). See the metric wire size chart for the other direction.
Voltage drop
For a two-wire DC or single-phase circuit, the drop is V = 2 × L × I × R, with L the one-way length and R the resistance per unit length. Example: 50 ft of 12 AWG at 15 A → 2 × 50 ft × 15 A × 1.588 Ω/1000 ft = 2.38 V, or 2.0 % of 120 V. The NEC recommends (informational notes to 210.19 and 215.2) no more than 3 % on a branch circuit and 5 % in total; low-voltage DC systems (12 V, 24 V) are far more sensitive, so long 12 V runs usually need two or three sizes heavier wire than the current alone suggests.
Aluminum, SWG and other gauges
Aluminum conductors follow the same AWG diameters but have about 61 % of copper's conductivity, so an aluminum conductor needs to be roughly two gauges larger for the same resistance. The British Standard Wire Gauge (SWG) and the old Birmingham gauge use different numbers: 14 SWG is 2.03 mm, not 1.63 mm. Sheet metal gauges are unrelated again.
Questions
What is the diameter of 12 AWG wire?
12 AWG solid wire is 0.0808 in (2.05 mm) in diameter, with a cross-section of 3.31 mm² (6530 circular mils). Stranded 12 AWG has the same copper area but measures about 0.092 in (2.3 mm) over the strands, before insulation.
What size wire for a 20 amp circuit?
12 AWG copper. NEC 240.4(D) limits 14 AWG to 15 A and 12 AWG to 20 A regardless of insulation rating. For long runs, check voltage drop: at 20 A, 12 AWG loses about 2.6 % of 120 V over 50 ft one way, so 10 AWG is the usual choice beyond roughly 55–60 ft.
How do I convert AWG to mm²?
Diameter in mm = 0.127 × 92^((36 − AWG)/39), then area = π/4 × d². Common pairs: 18 AWG = 0.82 mm², 16 AWG = 1.31 mm², 14 AWG = 2.08 mm², 12 AWG = 3.31 mm², 10 AWG = 5.26 mm², 8 AWG = 8.37 mm², 6 AWG = 13.3 mm². Metric cable comes in fixed sizes (1.5, 2.5, 4, 6, 10 …), so choose the next metric size up.
Is a higher gauge number thicker or thinner?
Thinner. 10 AWG is thicker than 14 AWG. The scale continues past 1 AWG as 1/0, 2/0, 3/0 and 4/0, which get thicker again; 4/0 is 0.46 in (11.7 mm).
Why is stranded wire thicker than solid wire of the same gauge?
The gauge fixes the copper area, not the outside diameter. Round strands leave gaps, so a 7-strand conductor is about 13 % larger in diameter than solid wire of equal area; 19-strand and fine-stranded flexible wire are similar or slightly larger, while compressed and compact stranding are smaller.
How many amps can 10 AWG wire carry?
Copper 10 AWG is listed at 30 A (60 °C), 35 A (75 °C) and 40 A (90 °C) in NEC Table 310.16, but the overcurrent protection is limited to 30 A by NEC 240.4(D). Bundling more than three current-carrying conductors or high ambient temperatures reduce this further.
Sources
- ASTM B258: Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors
- NFPA 70, National Electrical Code (2023), Table 310.16: Ampacities of insulated conductors, 60/75/90 °C
- IEC 60028:1925, International standard of resistance for copper (annealed copper: 1/58 Ω·mm²/m at 20 °C)
- IEC 60228:2023, Conductors of insulated cables (metric nominal cross-sections)
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.