TFFN Wire and Cable Specifications
US Cable Types · Fixture wire and flexible cord
TFFN: Thermoplastic Flexible Fixture wire, Nylon-jacketed. Voltage rating 600 V. Conductor insulation rated up to 90°C (194°F). Listed for dry locations. Covered by NEC Article 402; typical sizes 18 – 16 AWG.
- Voltage rating
- 600 V
- Max. conductor temp.
- 90°C194°F194°F90°C
- NEC article
- 402
Drawing
TFFN specifications
| Meaning of the letters | Thermoplastic Flexible Fixture wire, Nylon-jacketed |
|---|---|
| Voltage rating | 600 V |
| Max. conductor temp. | 90°C194°F |
| Locations | dry |
| Conductor insulation | PVC + nylon |
| NEC article | 402 |
| Sizes | 18 – 16 AWG |
TFFN is 18 or 16 AWG fixture wire for luminaire leads and wiring inside fixtures (NEC Article 402); 18 AWG is limited to 6 A and 16 AWG to 8 A (Table 402.5). It may not be used as branch-circuit wiring.
Other types in this group
All US Cable Types sizes
Sources
- NFPA 70, National Electrical Code (2023): Table 310.4(1); Articles 320, 330, 334, 336, 338, 340, 400, 402, 690
- Southwire: Romex SIMpull Type NM-B, spec 10028 (600 V, 90 °C conductors, 60 °C ampacity, jacket colour code)
- Southwire: Copper Service Entrance SER / SEU cable (XHHW-2, 90 °C wet or dry, grey PVC jacket)
- Southwire: RHH/RHW-2/USE-2 copper, spec 10010 (600 V, 90 °C wet or dry)
- UL 83 (thermoplastic insulated wires), UL 44 (thermoset), UL 719 (NM), UL 1569 (MC), UL 854 (SE/USE), UL 4703 (PV wire), UL 62 (flexible cords)
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.