US Wire and Cable Types (NEC)
The letters on North American wire are a code: T thermoplastic, X cross-linked, R rubber (thermoset), HH 90 °C, W wet-rated, N nylon jacket, -2 90 °C also when wet. So THWN-2 is a thermoplastic, nylon-jacketed conductor rated 90 °C wet or dry. Almost all building wire and cable here is 600 V.
Cable typesTap a type for its cross-section and full specs
| Type | Voltage ratingV | Max. conductor temp.°C°F | Ampacity limited to°C°F | Locations | Conductor insulation | Jacket / armor | NEC article | Sizes |
|---|---|---|---|---|---|---|---|---|
| Single conductors (building wire) | ||||||||
| THHN | 600 | 90194 | — | dry, damp | PVC + nylon | — | 310 | 14 AWG – 1000 kcmil |
| THWN-2 | 600 | 90194 | — | dry, damp, wet | PVC + nylon | — | 310 | 14 AWG – 1000 kcmil |
| XHHW-2 | 600 | 90194 | — | dry, damp, wet | XLPE (cross-linked PE) | — | 310 | 14 AWG – 1000 kcmil |
| RHW-2 | 600 | 90194 | — | dry, damp, wet | thermoset rubber (EPR/XLP) | — | 310 | 14 AWG – 1000 kcmil |
| USE-2 | 600 | 90194 | — | dry, wet, direct burial, sunlight-resistant | XLPE (cross-linked PE) | — | 338 | 14 AWG – 1000 kcmil |
| PV Wire | 600 / 1000 / 2000 V | 90194 | — | dry, wet, direct burial, sunlight-resistant | XLPE (cross-linked PE) | — | 690 | 18 AWG – 1000 kcmil |
| Cable assemblies | ||||||||
| NM-B (Romex) | 600 | 90194 | 60140 | dry | PVC + nylon | PVC jacket | 334 | 14 – 2 AWG Cu |
| UF-B | 600 | 90194 | 60140 | dry, wet, direct burial, sunlight-resistant | PVC + nylon | PVC jacket | 340 | 14 AWG – 4/0 AWG |
| MC Cable | 600 | 90194 | — | dry, damp | PVC + nylon | metal armor | 330 | 14 AWG – 1000 kcmil |
| AC Cable (BX) | 600 | 90194 | — | dry | PVC + nylon | metal armor | 320 | 14 – 1 AWG |
| SER | 600 | 90194 | — | dry, wet, sunlight-resistant | XLPE (cross-linked PE) | PVC jacket | 338 | 8 AWG – 4/0 AWG Cu, to 500 kcmil Al |
| SEU | 600 | 90194 | — | dry, wet, sunlight-resistant | XLPE (cross-linked PE) | PVC jacket | 338 | 8 AWG – 4/0 AWG Cu |
| TC (Tray Cable) | 600 | 90194 | — | dry, wet, sunlight-resistant | PVC + nylon | PVC jacket | 336 | 18 AWG – 1000 kcmil |
| Fixture wire and flexible cord | ||||||||
| TFFN | 600 | 90194 | — | dry | PVC + nylon | — | 402 | 18 – 16 AWG |
| SOOW | 600 | — | — | dry, wet | thermoset rubber (EPR/XLP) | rubber / TPE jacket | 400 | 18 – 2 AWG |
| SJOOW | 300 | — | — | dry, wet | thermoset rubber (EPR/XLP) | rubber / TPE jacket | 400 | 18 – 10 AWG |
No exact match. The nearest sizes:
How to read the type letters
Insulation material: T = thermoplastic (PVC), X = cross-linked polyethylene, R = thermoset rubber compound. Temperature: no H = 60 °C, H = 75 °C, HH = 90 °C. Location: W = wet locations; "-2" = the conductor keeps its 90 °C rating in wet locations (THWN-2, XHHW-2, RHW-2, USE-2). N = an outer nylon jacket for abrasion and oil/gasoline resistance.
Most wire is multiple-listed and printed with every type it meets, e.g. THHN/THWN-2 or RHH/RHW-2/USE-2. The most restrictive application decides which listing you rely on. THHN on its own is a dry/damp-location wire; for conduit outdoors or underground (always a wet location) you need the THWN-2 or XHHW-2 listing.
Cable assemblies are named by article: NM (non-metallic sheathed, "Romex"), UF (underground feeder), MC (metal-clad), AC (armored, "BX"), SE/SER/SEU (service entrance), TC (tray cable). The size is written conductors-and-ground: 12/2 with ground = two 12 AWG insulated conductors plus a bare ground; 12/3 = three insulated plus ground. SER is written by size, e.g. 4-4-4-6 = three 4 AWG plus a 6 AWG ground.
About US Cable Types
Voltage, temperature and location ratings above are from NEC Table 310.4(1) and the cable articles; size ranges are those of common product lines. All of these are 600 V except SJOOW (300 V) and PV wire (600, 1000 or 2000 V, as printed on the cable).
The insulation temperature is not the usable ampacity. Conductors are first limited by their terminations: NEC 110.14(C) requires the 60 °C column for circuits of 100 A or less and 14–1 AWG conductors unless the equipment is marked for 75 °C, which most breakers and receptacles now are. NM-B and UF-B are always limited to the 60 °C column (334.80, 340.80), even though NM-B conductors are 90 °C insulated; the 90 °C value is only used as the starting point for derating.
For conduit work the usual choice is THHN/THWN-2 copper (smaller diameter, slippery nylon jacket for pulling) or XHHW-2 (tougher, no nylon to damage, common for aluminum feeders). For buried runs without conduit use UF-B, USE-2 or a cable listed for direct burial; NM-B is dry-location only and may not be used in wet locations or buried, even inside conduit underground.
Flexible cords (SOOW, SJOOW, SJT, SPT) are for portable equipment and are not a substitute for fixed wiring (NEC 400.12): they may not run through walls, ceilings or floors.
NM-B jacket colors
Since 2001 US manufacturers color the NM-B jacket by conductor size. It is voluntary but nearly universal; some brands use other colors for 3-conductor cable, so read the print on the jacket.
| Jacket | Size | Typical breaker |
|---|---|---|
| White | 14 AWG | 15 A |
| Yellow | 12 AWG | 20 A |
| Orange | 10 AWG | 30 A |
| Black | 8 and 6 AWG | 40 A (8, 60 °C) · 55 A (6, 60 °C) |
| Gray | UF-B (any size) | — |
Which wire for which job
Typical residential and light-commercial choices:
| Job | Usual wire or cable |
|---|---|
| Branch circuits inside walls (dry) | NM-B (14/2, 12/2, 10/3 …) |
| Conduit indoors and outdoors | THHN/THWN-2 copper |
| Feeder or service conductors in conduit | XHHW-2 or THHN/THWN-2 (Cu or Al) |
| Service entrance on the outside wall | SEU or SER |
| Feed to a detached garage, buried | UF-B direct burial, or THWN-2 in conduit |
| Commercial walls and ceilings | MC (or AC) |
| Light fixture leads | TFFN / TFN |
| Portable equipment, temporary power | SOOW / SJOOW cord |
| Solar module strings | PV Wire / USE-2 |
Questions
What is the difference between THHN and THWN-2?
The construction is the same (PVC insulation with a nylon jacket); the listing differs. THHN is 90 °C in dry and damp locations; THWN-2 is 90 °C in wet locations too. Most wire is dual-listed THHN/THWN-2, so one spool covers both.
Can NM-B (Romex) be used outdoors or underground?
No. NM-B is for dry locations only (NEC 334.10, 334.12). Conduit underground or outdoors is a wet location, so use UF-B or individual THWN-2/XHHW-2 conductors in the conduit.
What do the NM-B jacket colors mean?
White = 14 AWG, yellow = 12 AWG, orange = 10 AWG, black = 8 and 6 AWG. Gray is UF-B, the burial-rated cable.
What is the difference between SER and SEU?
SER has an insulated neutral and a separate bare ground in a round jacket, so it can serve as a four-wire feeder to a subpanel. SEU has two insulated conductors and a bare concentric neutral, used for service entrance runs where neutral and ground are bonded.
What does the -2 mean in THWN-2 or XHHW-2?
The conductor is rated 90 °C in wet locations as well as dry. Without the -2, a W-rated conductor is limited to 75 °C when wet.
What voltage is THHN rated for?
600 V, like nearly all US building wire, NM-B, UF-B, MC and SER cable. Portable junior-service cords (SJ…) are 300 V.
Sources
- NFPA 70, National Electrical Code (2023): Table 310.4(1); Articles 320, 330, 334, 336, 338, 340, 400, 402, 690
- Southwire: Romex SIMpull Type NM-B, spec 10028 (600 V, 90 °C conductors, 60 °C ampacity, jacket colour code)
- Southwire: Copper Service Entrance SER / SEU cable (XHHW-2, 90 °C wet or dry, grey PVC jacket)
- Southwire: RHH/RHW-2/USE-2 copper, spec 10010 (600 V, 90 °C wet or dry)
- UL 83 (thermoplastic insulated wires), UL 44 (thermoset), UL 719 (NM), UL 1569 (MC), UL 854 (SE/USE), UL 4703 (PV wire), UL 62 (flexible cords)
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.