US Wire and Cable Types (NEC)

The letters on North American wire are a code: T thermoplastic, X cross-linked, R rubber (thermoset), HH 90 °C, W wet-rated, N nylon jacket, -2 90 °C also when wet. So THWN-2 is a thermoplastic, nylon-jacketed conductor rated 90 °C wet or dry. Almost all building wire and cable here is 600 V.

16 typesChecked 2026-11-155 sources
White: 14 AWG (15 A)Yellow: 12 AWG (20 A)Orange: 10 AWG (30 A)Black: 8 and 6 AWGGray: UF-B direct-burial cable
Jacket color by conductor size (voluntary US industry code since 2001). Check the print on the jacket.

Cable typesTap a type for its cross-section and full specs

16 of 16
TypeVoltage ratingVMax. conductor temp.°C°FAmpacity limited to°C°FLocationsConductor insulationJacket / armorNEC articleSizes
Single conductors (building wire)
THHN60090194—dry, dampPVC + nylon—31014 AWG – 1000 kcmil
THWN-260090194—dry, damp, wetPVC + nylon—31014 AWG – 1000 kcmil
XHHW-260090194—dry, damp, wetXLPE (cross-linked PE)—31014 AWG – 1000 kcmil
RHW-260090194—dry, damp, wetthermoset rubber (EPR/XLP)—31014 AWG – 1000 kcmil
USE-260090194—dry, wet, direct burial, sunlight-resistantXLPE (cross-linked PE)—33814 AWG – 1000 kcmil
PV Wire600 / 1000 / 2000 V90194—dry, wet, direct burial, sunlight-resistantXLPE (cross-linked PE)—69018 AWG – 1000 kcmil
Cable assemblies
NM-B (Romex)6009019460140dryPVC + nylonPVC jacket33414 – 2 AWG Cu
UF-B6009019460140dry, wet, direct burial, sunlight-resistantPVC + nylonPVC jacket34014 AWG – 4/0 AWG
MC Cable60090194—dry, dampPVC + nylonmetal armor33014 AWG – 1000 kcmil
AC Cable (BX)60090194—dryPVC + nylonmetal armor32014 – 1 AWG
SER60090194—dry, wet, sunlight-resistantXLPE (cross-linked PE)PVC jacket3388 AWG – 4/0 AWG Cu, to 500 kcmil Al
SEU60090194—dry, wet, sunlight-resistantXLPE (cross-linked PE)PVC jacket3388 AWG – 4/0 AWG Cu
TC (Tray Cable)60090194—dry, wet, sunlight-resistantPVC + nylonPVC jacket33618 AWG – 1000 kcmil
Fixture wire and flexible cord
TFFN60090194—dryPVC + nylon—40218 – 16 AWG
SOOW600——dry, wetthermoset rubber (EPR/XLP)rubber / TPE jacket40018 – 2 AWG
SJOOW300——dry, wetthermoset rubber (EPR/XLP)rubber / TPE jacket40018 – 10 AWG

How to read the type letters

Insulation material: T = thermoplastic (PVC), X = cross-linked polyethylene, R = thermoset rubber compound. Temperature: no H = 60 °C, H = 75 °C, HH = 90 °C. Location: W = wet locations; "-2" = the conductor keeps its 90 °C rating in wet locations (THWN-2, XHHW-2, RHW-2, USE-2). N = an outer nylon jacket for abrasion and oil/gasoline resistance.

Most wire is multiple-listed and printed with every type it meets, e.g. THHN/THWN-2 or RHH/RHW-2/USE-2. The most restrictive application decides which listing you rely on. THHN on its own is a dry/damp-location wire; for conduit outdoors or underground (always a wet location) you need the THWN-2 or XHHW-2 listing.

Cable assemblies are named by article: NM (non-metallic sheathed, "Romex"), UF (underground feeder), MC (metal-clad), AC (armored, "BX"), SE/SER/SEU (service entrance), TC (tray cable). The size is written conductors-and-ground: 12/2 with ground = two 12 AWG insulated conductors plus a bare ground; 12/3 = three insulated plus ground. SER is written by size, e.g. 4-4-4-6 = three 4 AWG plus a 6 AWG ground.

About US Cable Types

Voltage, temperature and location ratings above are from NEC Table 310.4(1) and the cable articles; size ranges are those of common product lines. All of these are 600 V except SJOOW (300 V) and PV wire (600, 1000 or 2000 V, as printed on the cable).

The insulation temperature is not the usable ampacity. Conductors are first limited by their terminations: NEC 110.14(C) requires the 60 °C column for circuits of 100 A or less and 14–1 AWG conductors unless the equipment is marked for 75 °C, which most breakers and receptacles now are. NM-B and UF-B are always limited to the 60 °C column (334.80, 340.80), even though NM-B conductors are 90 °C insulated; the 90 °C value is only used as the starting point for derating.

For conduit work the usual choice is THHN/THWN-2 copper (smaller diameter, slippery nylon jacket for pulling) or XHHW-2 (tougher, no nylon to damage, common for aluminum feeders). For buried runs without conduit use UF-B, USE-2 or a cable listed for direct burial; NM-B is dry-location only and may not be used in wet locations or buried, even inside conduit underground.

Flexible cords (SOOW, SJOOW, SJT, SPT) are for portable equipment and are not a substitute for fixed wiring (NEC 400.12): they may not run through walls, ceilings or floors.

NM-B jacket colors

Since 2001 US manufacturers color the NM-B jacket by conductor size. It is voluntary but nearly universal; some brands use other colors for 3-conductor cable, so read the print on the jacket.

JacketSizeTypical breaker
White14 AWG15 A
Yellow12 AWG20 A
Orange10 AWG30 A
Black8 and 6 AWG40 A (8, 60 °C) · 55 A (6, 60 °C)
GrayUF-B (any size)—

Which wire for which job

Typical residential and light-commercial choices:

JobUsual wire or cable
Branch circuits inside walls (dry)NM-B (14/2, 12/2, 10/3 …)
Conduit indoors and outdoorsTHHN/THWN-2 copper
Feeder or service conductors in conduitXHHW-2 or THHN/THWN-2 (Cu or Al)
Service entrance on the outside wallSEU or SER
Feed to a detached garage, buriedUF-B direct burial, or THWN-2 in conduit
Commercial walls and ceilingsMC (or AC)
Light fixture leadsTFFN / TFN
Portable equipment, temporary powerSOOW / SJOOW cord
Solar module stringsPV Wire / USE-2

Questions

What is the difference between THHN and THWN-2?

The construction is the same (PVC insulation with a nylon jacket); the listing differs. THHN is 90 °C in dry and damp locations; THWN-2 is 90 °C in wet locations too. Most wire is dual-listed THHN/THWN-2, so one spool covers both.

Can NM-B (Romex) be used outdoors or underground?

No. NM-B is for dry locations only (NEC 334.10, 334.12). Conduit underground or outdoors is a wet location, so use UF-B or individual THWN-2/XHHW-2 conductors in the conduit.

What do the NM-B jacket colors mean?

White = 14 AWG, yellow = 12 AWG, orange = 10 AWG, black = 8 and 6 AWG. Gray is UF-B, the burial-rated cable.

What is the difference between SER and SEU?

SER has an insulated neutral and a separate bare ground in a round jacket, so it can serve as a four-wire feeder to a subpanel. SEU has two insulated conductors and a bare concentric neutral, used for service entrance runs where neutral and ground are bonded.

What does the -2 mean in THWN-2 or XHHW-2?

The conductor is rated 90 °C in wet locations as well as dry. Without the -2, a W-rated conductor is limited to 75 °C when wet.

What voltage is THHN rated for?

600 V, like nearly all US building wire, NM-B, UF-B, MC and SER cable. Portable junior-service cords (SJ…) are 300 V.

Sources

  1. NFPA 70, National Electrical Code (2023): Table 310.4(1); Articles 320, 330, 334, 336, 338, 340, 400, 402, 690
  2. Southwire: Romex SIMpull Type NM-B, spec 10028 (600 V, 90 °C conductors, 60 °C ampacity, jacket colour code)
  3. Southwire: Copper Service Entrance SER / SEU cable (XHHW-2, 90 °C wet or dry, grey PVC jacket)
  4. Southwire: RHH/RHW-2/USE-2 copper, spec 10010 (600 V, 90 °C wet or dry)
  5. UL 83 (thermoplastic insulated wires), UL 44 (thermoset), UL 719 (NM), UL 1569 (MC), UL 854 (SE/USE), UL 4703 (PV wire), UL 62 (flexible cords)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.