1-1/2" ENT Conduit Dimensions & Fill
Conduit Sizes · ENT: electrical nonmetallic tubing
1-1/2" ENT conduit has a nominal inside diameter of 1.570 in (39.9 mm) and a total inside area of 1.936 in² (1,249 mm²). NEC Chapter 9 allows 0.774 in² (499 mm²) for three or more conductors (40 %), 0.600 in² (387 mm²) for two and 1.026 in² (662 mm²) for one.
- IDInside diameter (nominal)
- 39.9 mm1.570 in1.570 in39.9 mm
- A₄₀Fill area, over 2 wires (40 %)
- 499 mm²0.774 in²0.774 in²499 mm²
Drawing
1-1/2" ENT specifications
| Metric designator | 41 |
|---|---|
| IDInside diameter (nominal) | 1.570 in39.9 mm |
| ATotal inside area (100 %) | 1.936 in²1,249 mm² |
| A₄₀Fill area, over 2 wires (40 %) | 0.774 in²499 mm² |
| A₃₁Fill area, 2 wires (31 %) | 0.600 in²387 mm² |
| A₅₃Fill area, 1 wire (53 %) | 1.026 in²662 mm² |
Same trade size, other conduit types
All Conduit Sizes sizes
Sources
- NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
- NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
- Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
- Steel Tube Institute: Intermediate metal conduit
- PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
- IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.