MPO / MTP Fiber Optic Specifications
Fiber Optic Types · Connectors
MPO / MTP is a fiber optic connector with push-pull snap coupling. Fibers per connector: 8, 12, 16, 24 (to 72); polish flat (UPC), APC. Typical use: Parallel optics (40G/100G/400G SR4, SR8), trunk cables, high-density data centres.
- End face
- flat (UPC), APC
Drawing
MPO / MTP specifications
| Coupling | push-pull snap |
|---|---|
| Fibers | 8, 12, 16, 24 (to 72) |
| End face | flat (UPC), APC |
| Typical use | Parallel optics (40G/100G/400G SR4, SR8), trunk cables, high-density data centres |
MPO (IEC 61754-7, TIA-604-5) holds 8, 12, 16 or 24 fibers in one rectangular MT ferrule of 6.4 × 2.5 mm at 0.25 mm pitch. 40G/100G-SR4 uses 8 fibers of an MPO-12; 400G-SR8 uses MPO-16. Male connectors have two guide pins; the cable gender and polarity must match.
All Fiber Optic Types sizes
Sources
- ISO/IEC 11801-1:2017, Generic cabling: optical fibre cable categories OM1–OM5, OS1a, OS2
- ANSI/TIA-568.3-D: Optical Fiber Cabling and Components Standard (attenuation, connector colours)
- TIA-598-D: Optical fiber cable color coding (jacket colours)
- IEC 60793-2-10 (multimode A1) and IEC 60793-2-50 (single-mode B1.3); ITU-T G.652
- IEEE 802.3: 1000BASE-SX/LX, 10GBASE-SR/LR, 100GBASE-SR4 reach tables
- IEC 61754 series: Fibre optic connector interfaces (LC -20, SC -4, ST -2, FC -13, MPO -7, E2000 -15, MU -6)
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.