Fiber Optic Cable Types (OS2, OM1–OM5) and Connectors

Fiber is identified by its core size and jacket color: yellow = single-mode 9/125 µm (OS1/OS2, kilometres), orange = OM1/OM2, aqua = OM3/OM4, lime green = OM5 multimode 50/125 µm (tens to hundreds of metres). 10 Gbit/s runs 300 m on OM3, 400 m on OM4 and 10 km on OS2.

14 typesChecked 2026-11-156 sources
9/125 µmOS1 · OS250/125 µmOM2 – OM562.5/125 µmOM1OS1OS2OM1OM2OM3OM4OM5
Core (blue) inside the 125 µm cladding, drawn at one scale; jacket colors per TIA-598.

Fibers and connectorsTap a type for its end-face drawing and specs

14 of 14
TypeCoreµmCladdingµmJacket colorMin. modal bandwidth at 850 nm, MHz·km1 Gbit/s reachmft10 Gbit/s reachmft100 Gbit/s reach (SR4/LR4)mftFerrulemmCouplingFibersEnd face
Fiber types
OS19125yellow————————
OS29125yellow—5,00016,40410,00032,80810,00032,808————
OM162.5125orange20027590233108—————
OM250125orange5005501,80482269—————
OM350125aqua20005501,80430098470230————
OM450125aqua (violet from some makers)47005501,8044001,312100328————
OM550125lime green47005501,8044001,312100328————
Connectors
LC———————1.25push-pull latch1 (duplex clip for 2)UPC, APC
SC———————2.50push-pull snap1 (duplex clip for 2)UPC, APC
ST———————2.50bayonet twist-lock1PC, UPC
FC———————2.50threaded nut1UPC, APC
MPO / MTP————————push-pull snap8, 12, 16, 24 (to 72)flat (UPC), APC
E2000 (LSH)———————2.50push-pull snap1UPC, APC
MU———————1.25push-pull snap1UPC, APC

How to read fiber and connector designations

Core/cladding in micrometres: 9/125 is single-mode, 50/125 and 62.5/125 are multimode. The cladding is always 125 µm and the primary coating 250 µm (or 900 µm tight buffer), so all fibers look the same from outside. The jacket color and the print tell them apart.

OS = optical single-mode, OM = optical multimode (ISO/IEC 11801). OM3, OM4 and OM5 are "laser-optimised" for 850 nm VCSEL transceivers and are graded by effective modal bandwidth (MHz·km): the higher the number, the longer a given speed reaches. OS1 and OS2 differ by cable construction and loss (OS1 1.0 dB/km for indoor tight-buffered cable, OS2 0.4 dB/km for low-water-peak loose-tube cable).

Connector names describe the mechanical body; the polish is written after a slash: UPC (ultra physical contact, flat-domed, usually blue body on single-mode) or APC (angled 8°, green body, lower back-reflection, used for FTTH and video). Never mate APC with UPC: the angled faces leave an air gap and can damage the end faces. LC/UPC-LC/UPC duplex is the standard patch cord in data centres.

About Fiber Optic Types

The fiber rows list core and cladding size, the TIA-598 jacket color, the modal bandwidth and the IEEE 802.3 reach for 1, 10 and 100 Gbit/s (1000BASE-SX/LX, 10GBASE-SR/LR, 100GBASE-SR4/LR4). Reach values are per the IEEE standards with standard-grade transceivers; extended-reach optics go further.

Single-mode (OS2) costs about the same per metre as multimode today and has practically unlimited bandwidth; the optics are more expensive. It is the choice for campus backbones, anything over 400 m, FTTH and telecom. Multimode (OM3/OM4) uses cheaper short-reach optics and dominates inside data centres and buildings; OM5 adds the 850–953 nm window for SWDM optics that send four wavelengths over one duplex pair. OM1 and OM2 are legacy and should not be installed new.

Never mix 50 µm and 62.5 µm multimode in one link: a 62.5-into-50 µm joint loses several dB. OM2, OM3, OM4 and OM5 (all 50 µm) can be patched together, but the link performs to the lowest grade.

Connector ferrules come in two sizes: 2.5 mm (SC, ST, FC, E2000) and 1.25 mm small-form-factor (LC, MU), plus the rectangular MT ferrule of MPO/MTP with 8 to 24 fibers in a row. MTP is US Conec's trademarked high-performance MPO; both mate with each other. MPO connectors are male (with guide pins) or female, and trunk cables have a polarity method (A, B or C) that must match the cassettes and patch cords.

Connector body and boot colors (TIA-568.3)

Colors are a convention, not a guarantee. Read the cable print.

ColorMeaning
Beigemultimode OM1/OM2
Aquamultimode OM3 or OM4
Heather violet / erika violetmultimode OM4 (some makers)
Lime greenmultimode OM5
Bluesingle-mode, UPC polish
Greensingle-mode, APC (8°) polish

Typical loss budget values

For planning a link: cabled fiber per TIA-568.3-D maximum 3.5 dB/km at 850 nm and 1.5 dB/km at 1300 nm (multimode), 1.0 dB/km (OS1) or 0.4 dB/km (OS2) at 1310/1550 nm; mated connector pair max 0.75 dB; fusion splice max 0.3 dB. Short-reach 10GBASE-SR budgets are only a few dB, so every extra patch panel counts.

Questions

What is the difference between OM3 and OM4?

Both are 50/125 µm aqua multimode. OM4 has higher modal bandwidth (4700 vs 2000 MHz·km at 850 nm), so 10GBASE-SR reaches 400 m instead of 300 m and 100GBASE-SR4 100 m instead of 70 m.

What color is single-mode fiber?

Yellow jacket (TIA-598). Connectors are blue for UPC polish and green for APC. Multimode is orange (OM1/OM2), aqua (OM3/OM4, OM4 sometimes violet) or lime green (OM5).

How far can 10 Gbit/s go over fiber?

10GBASE-SR: 33 m on OM1, 82 m on OM2, 300 m on OM3, 400 m on OM4/OM5. 10GBASE-LR on single-mode OS2: 10 km; ER and ZR optics 40 and 80 km.

What is the difference between LC and SC connectors?

LC has a 1.25 mm ferrule and a latch, half the size of SC, which has a 2.5 mm ferrule and push-pull body. Performance is the same; LC dominates in switches and data centres, SC/APC in FTTH.

Can I connect APC and UPC connectors?

No. APC end faces are angled at 8°, UPC end faces are flat-domed. Mated together they leave an air gap with high loss and can damage the ferrules. Green = APC, blue = UPC on single-mode.

Sources

  1. ISO/IEC 11801-1:2017, Generic cabling: optical fibre cable categories OM1–OM5, OS1a, OS2
  2. ANSI/TIA-568.3-D: Optical Fiber Cabling and Components Standard (attenuation, connector colours)
  3. TIA-598-D: Optical fiber cable color coding (jacket colours)
  4. IEC 60793-2-10 (multimode A1) and IEC 60793-2-50 (single-mode B1.3); ITU-T G.652
  5. IEEE 802.3: 1000BASE-SX/LX, 10GBASE-SR/LR, 100GBASE-SR4 reach tables
  6. IEC 61754 series: Fibre optic connector interfaces (LC -20, SC -4, ST -2, FC -13, MPO -7, E2000 -15, MU -6)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.