120 mm² Wire: Resistance, Diameter, AWG
Metric Wire Sizes
A 120 mm² copper conductor (IEC 60228) may have at most 0.153 Ω/km (0.0466 Ω/1000 ft) DC resistance at 20 °C as a solid or stranded conductor (class 1 or 2), or 0.161 Ω/km (0.0491 Ω/1000 ft) as a flexible conductor (class 5). A solid round conductor of this area is 12.36 mm (0.4866 in) in diameter. The nearest AWG size is 250 kcmil.
- SNominal cross-section
- 120 mm²
- RMax. resistance, class 1/2 (solid, stranded)
- 0.153 Ω/km0.0466 Ω/1000 ft0.0466 Ω/1000 ft0.153 Ω/km
- RMax. resistance, class 5 (flexible)
- 0.161 Ω/km0.0491 Ω/1000 ft0.0491 Ω/1000 ft0.161 Ω/km
- Nearest AWG
- 250 kcmil
Drawing
120 mm² specifications
| SNominal cross-section | 120 mm² |
|---|---|
| dSolid conductor diameter (calc.) | 12.36 mm0.4866 in |
| Area in kcmil | 237 kcmil |
| RMax. resistance, class 1/2 (solid, stranded) | 0.153 Ω/km0.0466 Ω/1000 ft |
| RMax. resistance, class 5 (flexible) | 0.161 Ω/km0.0491 Ω/1000 ft |
| Nearest AWG | 250 kcmil |
| Smallest AWG with at least this area | 250 kcmil |
120 mm² (237 kcmil) has no close AWG size: it is 12 % more than 4/0 (107 mm²) and 5 % less than 250 kcmil (127 mm²).
All Metric Wire Sizes sizes
Sources
- IEC 60228:2023, Conductors of insulated cables (Tables 1, 2/4 and 5: class 1, 2 and 5 copper, maximum resistance at 20 °C)
- Lapp: T11 Conductor resistances and strand structure, metric (based on IEC/EN 60228)
- Bayka: Conductor resistance (IEC 60228 / VDE 0295)
- ASTM B258: AWG nominal diameters and areas (for the AWG comparison)
Values last checked against these sources on November 15, 2026. · How we check data