Metric Wire Size Chart (mm²)
Metric cable is sized by nominal cross-section in mm², from 0.5 to 300 mm² and beyond, as defined in IEC 60228. The nominal size is really a resistance class: a 2.5 mm² stranded conductor is one that measures no more than 7.41 Ω/km at 20 °C.
Size chartTap a size for its drawing and full specs
| Size | dSolid conductor diameter (calc.)mmin | Area in kcmilkcmil | RMax. resistance, class 1/2 (solid, stranded)Ω/kmΩ/1000 ft | RMax. resistance, class 5 (flexible)Ω/kmΩ/1000 ft | Nearest AWG | Smallest AWG with at least this area |
|---|---|---|---|---|---|---|
| 0.5 mm² | 0.800.0315 | 0.987 | 3610.9728 | 3911.8872 | 20 AWG | 20 AWG |
| 0.75 mm² | 0.980.0386 | 1.48 | 24.57.4676 | 267.9248 | 18 AWG | 18 AWG |
| 1 mm² | 1.130.0445 | 1.97 | 18.15.5169 | 19.55.9436 | 18 AWG | 16 AWG |
| 1.5 mm² | 1.380.0543 | 2.96 | 12.13.6881 | 13.34.0538 | 16 AWG | 14 AWG |
| 2.5 mm² | 1.780.0701 | 4.93 | 7.412.2586 | 7.982.4323 | 14 AWG | 12 AWG |
| 4 mm² | 2.260.0890 | 7.89 | 4.611.4051 | 4.951.5088 | 12 AWG | 10 AWG |
| 6 mm² | 2.760.1087 | 11.8 | 3.080.9388 | 3.31.0058 | 10 AWG | 8 AWG |
| 10 mm² | 3.570.1406 | 19.7 | 1.830.5578 | 1.910.5822 | 8 AWG | 6 AWG |
| 16 mm² | 4.510.1776 | 31.6 | 1.150.3505 | 1.210.3688 | 6 AWG | 4 AWG |
| 25 mm² | 5.640.2220 | 49.3 | 0.7270.2216 | 0.780.2377 | 4 AWG | 2 AWG |
| 35 mm² | 6.680.2630 | 69.1 | 0.5240.1597 | 0.5540.1689 | 2 AWG | 1 AWG |
| 50 mm² | 7.980.3142 | 98.7 | 0.3870.1180 | 0.3860.1177 | 1/0 AWG | 1/0 AWG |
| 70 mm² | 9.440.3717 | 138 | 0.2680.0817 | 0.2720.0829 | 2/0 AWG | 3/0 AWG |
| 95 mm² | 11.000.4331 | 187 | 0.1930.0588 | 0.2060.0628 | 3/0 AWG | 4/0 AWG |
| 120 mm² | 12.360.4866 | 237 | 0.1530.0466 | 0.1610.0491 | 250 kcmil | 250 kcmil |
| 150 mm² | 13.820.5441 | 296 | 0.1240.0378 | 0.1290.0393 | 300 kcmil | 300 kcmil |
| 185 mm² | 15.350.6043 | 365 | 0.09910.0302 | 0.1060.0323 | 350 kcmil | 400 kcmil |
| 240 mm² | 17.480.6882 | 474 | 0.07540.0230 | 0.08010.0244 | 500 kcmil | 500 kcmil |
| 300 mm² | 19.540.7693 | 592 | 0.06010.0183 | 0.06410.0195 | 600 kcmil | 600 kcmil |
No exact match. The nearest sizes:
How metric conductor sizes are defined
IEC 60228 does not specify a measured area. For each nominal size it sets a maximum DC resistance at 20 °C and, for stranded conductors, a minimum number of wires. A manufacturer may use slightly less copper as long as the conductor passes the resistance test, so measuring and calculating the area of a real cable usually gives a value a few per cent under the nominal size.
The standard groups conductors into classes. Class 1 is solid, class 2 stranded (house wiring such as H07V-R, power cables), class 5 flexible fine-stranded (cords, H05VV-F, H07RN-F, welding leads) and class 6 extra-flexible. Classes 1 and 2 share one resistance table; classes 5 and 6 share another, a few per cent higher, because fine strands have more twist and a longer path. Tinned copper has its own, slightly higher limits.
On a cable the size appears in the marking, e.g. 3G2.5 = three cores of 2.5 mm² including the green-yellow protective conductor (G), or 4×1.5 = four cores without one. The diameter column is the calculated diameter of a solid round conductor of exactly the nominal area, useful for checking a solid wire with a caliper. Stranded conductors are larger over the strands; compacted ones close to the solid value.
About Metric Wire Sizes
The table lists the standard IEC 60228 nominal cross-sections from 0.5 mm² to 300 mm² with the maximum DC resistance of plain (uncoated) annealed copper at 20 °C, the value every compliant cable must meet. Use it to check a measured conductor, to compute voltage drop, or to compare a metric cable with an AWG one.
To correct the resistance for temperature, multiply by 1 + 0.00393 × (t − 20). At 70 °C, the normal maximum for PVC insulation, a conductor has about 20 % more resistance than the table value. For voltage drop in a two-wire circuit, use twice the one-way length.
The AWG columns compare by copper area. Metric and AWG sizes never match exactly: 2.5 mm² lies between 14 AWG (2.08 mm²) and 12 AWG (3.31 mm²), and 1.5 mm² between 16 AWG (1.31 mm²) and 14 AWG (2.08 mm²). The nearest-AWG column picks the closest stocked size; the last column gives the smallest AWG or kcmil size with at least the same area, which is the safe choice when replacing a metric conductor. Above 4/0 the North American sizes are in kcmil.
Current-carrying capacity is not part of IEC 60228. It depends on the installation method, insulation, grouping and ambient temperature, and is tabulated in IEC 60364-5-52 (and national versions such as BS 7671 Appendix 4 or DIN VDE 0298-4). As a rough guide for PVC-insulated copper in conduit, 1.5 mm² is typically protected at 13–16 A, 2.5 mm² at 16–20 A and 4 mm² at 25–32 A. Always check the table for your installation method.
Sizes outside this table
IEC 60228 also lists 400 to 2500 mm² for power cables, and some countries use extra sizes: 0.14, 0.25 and 0.34 mm² are common in control and data cables (DIN VDE 0295 class 5/6), and 0.2 mm² appears in electronics. Their resistance limits come from the same standard or from DIN VDE 0295.
Questions
What is 2.5 mm² in AWG?
2.5 mm² is between 14 AWG (2.08 mm²) and 12 AWG (3.31 mm²), roughly 13 AWG, which is rarely stocked. For substitution by current capacity, 2.5 mm² can replace 14 AWG, and 12 AWG can replace 2.5 mm².
What is the resistance of 1.5 mm² copper wire?
At most 12.1 Ω/km (0.0121 Ω/m) at 20 °C for solid or stranded copper, and 13.3 Ω/km for flexible class 5 conductors, per IEC 60228. At 70 °C operating temperature that rises by about 20 %.
What is the diameter of a 2.5 mm² wire?
A solid 2.5 mm² conductor is about 1.78 mm in diameter (√(4 × 2.5/π)). A 7-strand class 2 conductor measures about 2.0 mm over the strands, and fine-stranded flexible conductors are similar. With PVC insulation a single core is around 3.5 mm.
Why does my cable measure less than its nominal mm²?
Because IEC 60228 defines sizes by maximum resistance, not by area. A conductor that meets the 7.41 Ω/km limit is a valid 2.5 mm² conductor even if its copper area is 2.4 mm². A conductor that measures far below its size and fails the resistance limit is undersized (a known issue with counterfeit cable and CCA, copper-clad aluminum).
How do I convert mm² to AWG?
Find the gauge whose area is closest: n = 36 − 39 × log₉₂(d / 0.127 mm), with d = √(4A/π). In practice use the table: 0.75 mm² ≈ 18 AWG, 1.5 mm² ≈ 16 AWG, 2.5 mm² ≈ 14 AWG, 4 mm² ≈ 12 AWG, 6 mm² ≈ 10 AWG, 10 mm² ≈ 8 AWG, 16 mm² ≈ 6 AWG, 25 mm² ≈ 4 AWG, 35 mm² ≈ 2 AWG, 50 mm² ≈ 1/0.
Sources
- IEC 60228:2023, Conductors of insulated cables (Tables 1, 2/4 and 5: class 1, 2 and 5 copper, maximum resistance at 20 °C)
- Lapp: T11 Conductor resistances and strand structure, metric (based on IEC/EN 60228)
- Bayka: Conductor resistance (IEC 60228 / VDE 0295)
- ASTM B258: AWG nominal diameters and areas (for the AWG comparison)
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.