Metric Wire Size Chart (mm²)

Metric cable is sized by nominal cross-section in mm², from 0.5 to 300 mm² and beyond, as defined in IEC 60228. The nominal size is really a resistance class: a 2.5 mm² stranded conductor is one that measures no more than 7.41 Ω/km at 20 °C.

19 sizesChecked 2026-11-154 sources
Each circle has the nominal copper area of the size (solid round equivalent).Drawn to scale

Size chartTap a size for its drawing and full specs

19 of 19
SizedSolid conductor diameter (calc.)mminArea in kcmilkcmilRMax. resistance, class 1/2 (solid, stranded)Ω/kmΩ/1000 ftRMax. resistance, class 5 (flexible)Ω/kmΩ/1000 ftNearest AWGSmallest AWG with at least this area
0.5 mm²0.800.03150.9873610.97283911.887220 AWG20 AWG
0.75 mm²0.980.03861.4824.57.4676267.924818 AWG18 AWG
1 mm²1.130.04451.9718.15.516919.55.943618 AWG16 AWG
1.5 mm²1.380.05432.9612.13.688113.34.053816 AWG14 AWG
2.5 mm²1.780.07014.937.412.25867.982.432314 AWG12 AWG
4 mm²2.260.08907.894.611.40514.951.508812 AWG10 AWG
6 mm²2.760.108711.83.080.93883.31.005810 AWG8 AWG
10 mm²3.570.140619.71.830.55781.910.58228 AWG6 AWG
16 mm²4.510.177631.61.150.35051.210.36886 AWG4 AWG
25 mm²5.640.222049.30.7270.22160.780.23774 AWG2 AWG
35 mm²6.680.263069.10.5240.15970.5540.16892 AWG1 AWG
50 mm²7.980.314298.70.3870.11800.3860.11771/0 AWG1/0 AWG
70 mm²9.440.37171380.2680.08170.2720.08292/0 AWG3/0 AWG
95 mm²11.000.43311870.1930.05880.2060.06283/0 AWG4/0 AWG
120 mm²12.360.48662370.1530.04660.1610.0491250 kcmil250 kcmil
150 mm²13.820.54412960.1240.03780.1290.0393300 kcmil300 kcmil
185 mm²15.350.60433650.09910.03020.1060.0323350 kcmil400 kcmil
240 mm²17.480.68824740.07540.02300.08010.0244500 kcmil500 kcmil
300 mm²19.540.76935920.06010.01830.06410.0195600 kcmil600 kcmil

How metric conductor sizes are defined

IEC 60228 does not specify a measured area. For each nominal size it sets a maximum DC resistance at 20 °C and, for stranded conductors, a minimum number of wires. A manufacturer may use slightly less copper as long as the conductor passes the resistance test, so measuring and calculating the area of a real cable usually gives a value a few per cent under the nominal size.

The standard groups conductors into classes. Class 1 is solid, class 2 stranded (house wiring such as H07V-R, power cables), class 5 flexible fine-stranded (cords, H05VV-F, H07RN-F, welding leads) and class 6 extra-flexible. Classes 1 and 2 share one resistance table; classes 5 and 6 share another, a few per cent higher, because fine strands have more twist and a longer path. Tinned copper has its own, slightly higher limits.

On a cable the size appears in the marking, e.g. 3G2.5 = three cores of 2.5 mm² including the green-yellow protective conductor (G), or 4×1.5 = four cores without one. The diameter column is the calculated diameter of a solid round conductor of exactly the nominal area, useful for checking a solid wire with a caliper. Stranded conductors are larger over the strands; compacted ones close to the solid value.

About Metric Wire Sizes

The table lists the standard IEC 60228 nominal cross-sections from 0.5 mm² to 300 mm² with the maximum DC resistance of plain (uncoated) annealed copper at 20 °C, the value every compliant cable must meet. Use it to check a measured conductor, to compute voltage drop, or to compare a metric cable with an AWG one.

To correct the resistance for temperature, multiply by 1 + 0.00393 × (t − 20). At 70 °C, the normal maximum for PVC insulation, a conductor has about 20 % more resistance than the table value. For voltage drop in a two-wire circuit, use twice the one-way length.

The AWG columns compare by copper area. Metric and AWG sizes never match exactly: 2.5 mm² lies between 14 AWG (2.08 mm²) and 12 AWG (3.31 mm²), and 1.5 mm² between 16 AWG (1.31 mm²) and 14 AWG (2.08 mm²). The nearest-AWG column picks the closest stocked size; the last column gives the smallest AWG or kcmil size with at least the same area, which is the safe choice when replacing a metric conductor. Above 4/0 the North American sizes are in kcmil.

Current-carrying capacity is not part of IEC 60228. It depends on the installation method, insulation, grouping and ambient temperature, and is tabulated in IEC 60364-5-52 (and national versions such as BS 7671 Appendix 4 or DIN VDE 0298-4). As a rough guide for PVC-insulated copper in conduit, 1.5 mm² is typically protected at 13–16 A, 2.5 mm² at 16–20 A and 4 mm² at 25–32 A. Always check the table for your installation method.

Sizes outside this table

IEC 60228 also lists 400 to 2500 mm² for power cables, and some countries use extra sizes: 0.14, 0.25 and 0.34 mm² are common in control and data cables (DIN VDE 0295 class 5/6), and 0.2 mm² appears in electronics. Their resistance limits come from the same standard or from DIN VDE 0295.

Questions

What is 2.5 mm² in AWG?

2.5 mm² is between 14 AWG (2.08 mm²) and 12 AWG (3.31 mm²), roughly 13 AWG, which is rarely stocked. For substitution by current capacity, 2.5 mm² can replace 14 AWG, and 12 AWG can replace 2.5 mm².

What is the resistance of 1.5 mm² copper wire?

At most 12.1 Ω/km (0.0121 Ω/m) at 20 °C for solid or stranded copper, and 13.3 Ω/km for flexible class 5 conductors, per IEC 60228. At 70 °C operating temperature that rises by about 20 %.

What is the diameter of a 2.5 mm² wire?

A solid 2.5 mm² conductor is about 1.78 mm in diameter (√(4 × 2.5/π)). A 7-strand class 2 conductor measures about 2.0 mm over the strands, and fine-stranded flexible conductors are similar. With PVC insulation a single core is around 3.5 mm.

Why does my cable measure less than its nominal mm²?

Because IEC 60228 defines sizes by maximum resistance, not by area. A conductor that meets the 7.41 Ω/km limit is a valid 2.5 mm² conductor even if its copper area is 2.4 mm². A conductor that measures far below its size and fails the resistance limit is undersized (a known issue with counterfeit cable and CCA, copper-clad aluminum).

How do I convert mm² to AWG?

Find the gauge whose area is closest: n = 36 − 39 × log₉₂(d / 0.127 mm), with d = √(4A/π). In practice use the table: 0.75 mm² ≈ 18 AWG, 1.5 mm² ≈ 16 AWG, 2.5 mm² ≈ 14 AWG, 4 mm² ≈ 12 AWG, 6 mm² ≈ 10 AWG, 10 mm² ≈ 8 AWG, 16 mm² ≈ 6 AWG, 25 mm² ≈ 4 AWG, 35 mm² ≈ 2 AWG, 50 mm² ≈ 1/0.

Sources

  1. IEC 60228:2023, Conductors of insulated cables (Tables 1, 2/4 and 5: class 1, 2 and 5 copper, maximum resistance at 20 °C)
  2. Lapp: T11 Conductor resistances and strand structure, metric (based on IEC/EN 60228)
  3. Bayka: Conductor resistance (IEC 60228 / VDE 0295)
  4. ASTM B258: AWG nominal diameters and areas (for the AWG comparison)

Values last checked against these sources on November 15, 2026. · How we check data