185 mm² Wire: Resistance, Diameter, AWG

Metric Wire Sizes

A 185 mm² copper conductor (IEC 60228) may have at most 0.0991 Ω/km (0.0302 Ω/1000 ft) DC resistance at 20 °C as a solid or stranded conductor (class 1 or 2), or 0.106 Ω/km (0.0323 Ω/1000 ft) as a flexible conductor (class 5). A solid round conductor of this area is 15.35 mm (0.6043 in) in diameter. The nearest AWG size is 350 kcmil.

SNominal cross-section
185 mm²
RMax. resistance, class 1/2 (solid, stranded)
0.0991 Ω/km0.0302 Ω/1000 ft0.0302 Ω/1000 ft0.0991 Ω/km
RMax. resistance, class 5 (flexible)
0.106 Ω/km0.0323 Ω/1000 ft0.0323 Ω/1000 ft0.106 Ω/km
Nearest AWG
350 kcmil

Drawing

⌀15.35 mm⌀0.6043 in185 mm²Solid round conductor, nominal area
185 mm² / 350 kcmil350 kcmil: 177.3 mm² (-4 %)
Left: solid round conductor of the nominal area. Right: the same with the nearest AWG / kcmil size overlaid (orange).Drawn to scale · Dimensions in mmDimensions in inches

185 mm² specifications

SNominal cross-section185 mm²
dSolid conductor diameter (calc.)15.35 mm0.6043 in
Area in kcmil365 kcmil
RMax. resistance, class 1/2 (solid, stranded)0.0991 Ω/km0.0302 Ω/1000 ft
RMax. resistance, class 5 (flexible)0.106 Ω/km0.0323 Ω/1000 ft
Nearest AWG350 kcmil
Smallest AWG with at least this area400 kcmil

All Metric Wire Sizes sizes

Compare all 19 sizes in the Metric Wire Sizes chart →

Sources

  1. IEC 60228:2023, Conductors of insulated cables (Tables 1, 2/4 and 5: class 1, 2 and 5 copper, maximum resistance at 20 °C)
  2. Lapp: T11 Conductor resistances and strand structure, metric (based on IEC/EN 60228)
  3. Bayka: Conductor resistance (IEC 60228 / VDE 0295)
  4. ASTM B258: AWG nominal diameters and areas (for the AWG comparison)

Values last checked against these sources on November 15, 2026. · How we check data