12 AWG Wire Size
AWG Wire Gauge
12 AWG solid wire is 0.0808 in (2.052 mm) in diameter, with a copper cross-section of 3.309 mm² (6,530 circular mils). Solid annealed copper of this size has a DC resistance of 5.211 Ω/km (1.588 Ω/1000 ft) at 20 °C.
- dDiameter
- 2.052 mm0.0808 in0.0808 in2.052 mm
- ACross-section
- 3.309 mm²
- RDC resistance, copper 20 °C
- 5.211 Ω/km
- Ampacity 75 °C (NEC)
- 25 A
Drawing
12 AWG specifications
| dDiameter | 0.0808 in2.052 mm |
|---|---|
| ACross-section | 3.309 mm² |
| Circular mils | 6,530 |
| RDC resistance, copper 20 °C | 5.211 Ω/km |
| RDC resistance, copper 20 °C | 1.588 Ω/1000 ft |
| Ampacity 60 °C (NEC) | 20 A |
| Ampacity 75 °C (NEC) | 25 A |
| Ampacity 90 °C (NEC) | 30 A |
| Next metric size up | 4 mm² |
12 AWG is the standard size for 20 A circuits (kitchen, bathroom and laundry receptacles in the US). Metric 4 mm² has slightly more copper; 2.5 mm² has less and is not a substitute on a 20 A breaker.
Also known as
#12
Metric (IEC 60228) size with at least the same area
All AWG Wire Gauge sizes
Sources
- ASTM B258: Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors
- NFPA 70, National Electrical Code (2023), Table 310.16: Ampacities of insulated conductors, 60/75/90 °C
- IEC 60028:1925, International standard of resistance for copper (annealed copper: 1/58 Ω·mm²/m at 20 °C)
- IEC 60228:2023, Conductors of insulated cables (metric nominal cross-sections)
Values last checked against these sources on November 15, 2026. · How we check data