4 mm² Wire: Resistance, Diameter, AWG
Metric Wire Sizes
A 4 mm² copper conductor (IEC 60228) may have at most 4.61 Ω/km (1.4051 Ω/1000 ft) DC resistance at 20 °C as a solid or stranded conductor (class 1 or 2), or 4.95 Ω/km (1.5088 Ω/1000 ft) as a flexible conductor (class 5). A solid round conductor of this area is 2.26 mm (0.0890 in) in diameter. The nearest AWG size is 12 AWG.
- SNominal cross-section
- 4 mm²
- RMax. resistance, class 1/2 (solid, stranded)
- 4.61 Ω/km1.4051 Ω/1000 ft1.4051 Ω/1000 ft4.61 Ω/km
- RMax. resistance, class 5 (flexible)
- 4.95 Ω/km1.5088 Ω/1000 ft1.5088 Ω/1000 ft4.95 Ω/km
- Nearest AWG
- 12 AWG
Drawing
4 mm² specifications
| SNominal cross-section | 4 mm² |
|---|---|
| dSolid conductor diameter (calc.) | 2.26 mm0.0890 in |
| Area in kcmil | 7.89 kcmil |
| RMax. resistance, class 1/2 (solid, stranded) | 4.61 Ω/km1.4051 Ω/1000 ft |
| RMax. resistance, class 5 (flexible) | 4.95 Ω/km1.5088 Ω/1000 ft |
| Nearest AWG | 12 AWG |
| Smallest AWG with at least this area | 10 AWG |
4 mm² is common for 20–32 A radial circuits, outdoor feeds, and photovoltaic string cable (4 mm² and 6 mm² PV cable).
Comparable AWG sizes
All Metric Wire Sizes sizes
Sources
- IEC 60228:2023, Conductors of insulated cables (Tables 1, 2/4 and 5: class 1, 2 and 5 copper, maximum resistance at 20 °C)
- Lapp: T11 Conductor resistances and strand structure, metric (based on IEC/EN 60228)
- Bayka: Conductor resistance (IEC 60228 / VDE 0295)
- ASTM B258: AWG nominal diameters and areas (for the AWG comparison)
Values last checked against these sources on November 15, 2026. · How we check data