14 AWG Wire Size

AWG Wire Gauge

14 AWG solid wire is 0.0641 in (1.628 mm) in diameter, with a copper cross-section of 2.081 mm² (4,107 circular mils). Solid annealed copper of this size has a DC resistance of 8.285 Ω/km (2.525 Ω/1000 ft) at 20 °C.

dDiameter
1.628 mm0.0641 in0.0641 in1.628 mm
ACross-section
2.081 mm²
RDC resistance, copper 20 °C
8.285 Ω/km
Ampacity 75 °C (NEC)
20 A

Drawing

⌀1.628 mm⌀0.0641 inSolid2.081 mm²
⌀1.846 mm⌀0.0727 in7 × ⌀0.615 mm⌀0.0242 in7 strands, same area
Bare conductor without insulation; 7-strand shown as an uncompressed concentric lay.Drawn to scale · Dimensions in mmDimensions in inches

14 AWG specifications

dDiameter0.0641 in1.628 mm
ACross-section2.081 mm²
Circular mils4,107
RDC resistance, copper 20 °C8.285 Ω/km
RDC resistance, copper 20 °C2.525 Ω/1000 ft
Ampacity 60 °C (NEC)15 A
Ampacity 75 °C (NEC)20 A
Ampacity 90 °C (NEC)25 A
Next metric size up2.5 mm²

14 AWG is the smallest size allowed for general branch circuits in US homes, on a 15 A breaker (NEC 240.4(D)), even though the 60 °C table ampacity is 15 A and the 75 °C value 20 A. The nearest metric sizes are 1.5 mm² (smaller) and 2.5 mm² (larger).

Also known as

#14

Metric (IEC 60228) size with at least the same area

All AWG Wire Gauge sizes

Compare all 44 sizes in the AWG Wire Gauge chart →

Sources

  1. ASTM B258: Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors
  2. NFPA 70, National Electrical Code (2023), Table 310.16: Ampacities of insulated conductors, 60/75/90 °C
  3. IEC 60028:1925, International standard of resistance for copper (annealed copper: 1/58 Ω·mm²/m at 20 °C)
  4. IEC 60228:2023, Conductors of insulated cables (metric nominal cross-sections)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.