2.5 mm² Wire: Resistance, Diameter, AWG
Metric Wire Sizes
A 2.5 mm² copper conductor (IEC 60228) may have at most 7.41 Ω/km (2.2586 Ω/1000 ft) DC resistance at 20 °C as a solid or stranded conductor (class 1 or 2), or 7.98 Ω/km (2.4323 Ω/1000 ft) as a flexible conductor (class 5). A solid round conductor of this area is 1.78 mm (0.0701 in) in diameter. The nearest AWG size is 14 AWG.
- SNominal cross-section
- 2.5 mm²
- RMax. resistance, class 1/2 (solid, stranded)
- 7.41 Ω/km2.2586 Ω/1000 ft2.2586 Ω/1000 ft7.41 Ω/km
- RMax. resistance, class 5 (flexible)
- 7.98 Ω/km2.4323 Ω/1000 ft2.4323 Ω/1000 ft7.98 Ω/km
- Nearest AWG
- 14 AWG
Drawing
2.5 mm² specifications
| SNominal cross-section | 2.5 mm² |
|---|---|
| dSolid conductor diameter (calc.) | 1.78 mm0.0701 in |
| Area in kcmil | 4.93 kcmil |
| RMax. resistance, class 1/2 (solid, stranded) | 7.41 Ω/km2.2586 Ω/1000 ft |
| RMax. resistance, class 5 (flexible) | 7.98 Ω/km2.4323 Ω/1000 ft |
| Nearest AWG | 14 AWG |
| Smallest AWG with at least this area | 12 AWG |
2.5 mm² is the usual size for socket circuits in Europe: 16 A circuits in Germany, 20 A circuits in France, and the UK 32 A ring final circuit (where two parallel legs share the load). It has 20 % more copper than 14 AWG but less than 12 AWG, so it is not a substitute for 12 AWG on a US 20 A circuit.
Comparable AWG sizes
All Metric Wire Sizes sizes
Sources
- IEC 60228:2023, Conductors of insulated cables (Tables 1, 2/4 and 5: class 1, 2 and 5 copper, maximum resistance at 20 °C)
- Lapp: T11 Conductor resistances and strand structure, metric (based on IEC/EN 60228)
- Bayka: Conductor resistance (IEC 60228 / VDE 0295)
- ASTM B258: AWG nominal diameters and areas (for the AWG comparison)
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.