2.5 mm² Wire: Resistance, Diameter, AWG

Metric Wire Sizes

A 2.5 mm² copper conductor (IEC 60228) may have at most 7.41 Ω/km (2.2586 Ω/1000 ft) DC resistance at 20 °C as a solid or stranded conductor (class 1 or 2), or 7.98 Ω/km (2.4323 Ω/1000 ft) as a flexible conductor (class 5). A solid round conductor of this area is 1.78 mm (0.0701 in) in diameter. The nearest AWG size is 14 AWG.

SNominal cross-section
2.5 mm²
RMax. resistance, class 1/2 (solid, stranded)
7.41 Ω/km2.2586 Ω/1000 ft2.2586 Ω/1000 ft7.41 Ω/km
RMax. resistance, class 5 (flexible)
7.98 Ω/km2.4323 Ω/1000 ft2.4323 Ω/1000 ft7.98 Ω/km
Nearest AWG
14 AWG

Drawing

⌀1.78 mm⌀0.0701 in2.5 mm²Solid round conductor, nominal area
2.5 mm² / 14 AWG14 AWG: 2.08 mm² (-17 %)
Left: solid round conductor of the nominal area. Right: the same with the nearest AWG / kcmil size overlaid (orange).Drawn to scale · Dimensions in mmDimensions in inches

2.5 mm² specifications

SNominal cross-section2.5 mm²
dSolid conductor diameter (calc.)1.78 mm0.0701 in
Area in kcmil4.93 kcmil
RMax. resistance, class 1/2 (solid, stranded)7.41 Ω/km2.2586 Ω/1000 ft
RMax. resistance, class 5 (flexible)7.98 Ω/km2.4323 Ω/1000 ft
Nearest AWG14 AWG
Smallest AWG with at least this area12 AWG

2.5 mm² is the usual size for socket circuits in Europe: 16 A circuits in Germany, 20 A circuits in France, and the UK 32 A ring final circuit (where two parallel legs share the load). It has 20 % more copper than 14 AWG but less than 12 AWG, so it is not a substitute for 12 AWG on a US 20 A circuit.

Comparable AWG sizes

All Metric Wire Sizes sizes

Compare all 19 sizes in the Metric Wire Sizes chart →

Sources

  1. IEC 60228:2023, Conductors of insulated cables (Tables 1, 2/4 and 5: class 1, 2 and 5 copper, maximum resistance at 20 °C)
  2. Lapp: T11 Conductor resistances and strand structure, metric (based on IEC/EN 60228)
  3. Bayka: Conductor resistance (IEC 60228 / VDE 0295)
  4. ASTM B258: AWG nominal diameters and areas (for the AWG comparison)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.