16 AWG Wire Size

AWG Wire Gauge

16 AWG solid wire is 0.0508 in (1.290 mm) in diameter, with a copper cross-section of 1.309 mm² (2,583 circular mils). Solid annealed copper of this size has a DC resistance of 13.17 Ω/km (4.015 Ω/1000 ft) at 20 °C.

dDiameter
1.290 mm0.0508 in0.0508 in1.290 mm
ACross-section
1.309 mm²
RDC resistance, copper 20 °C
13.17 Ω/km

Drawing

⌀1.290 mm⌀0.0508 inSolid1.309 mm²
⌀1.463 mm⌀0.0576 in7 × ⌀0.488 mm⌀0.0192 in7 strands, same area
Bare conductor without insulation; 7-strand shown as an uncompressed concentric lay.Drawn to scale · Dimensions in mmDimensions in inches

16 AWG specifications

dDiameter0.0508 in1.290 mm
ACross-section1.309 mm²
Circular mils2,583
RDC resistance, copper 20 °C13.17 Ω/km
RDC resistance, copper 20 °C4.015 Ω/1000 ft
Next metric size up1.5 mm²

16 AWG is typical for extension cords up to 13 A (US cord rules, not Table 310.16), speaker wire and 12 V automotive circuits up to about 10 A over short runs.

Also known as

#16

Metric (IEC 60228) size with at least the same area

All AWG Wire Gauge sizes

Compare all 44 sizes in the AWG Wire Gauge chart →

Sources

  1. ASTM B258: Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors
  2. NFPA 70, National Electrical Code (2023), Table 310.16: Ampacities of insulated conductors, 60/75/90 °C
  3. IEC 60028:1925, International standard of resistance for copper (annealed copper: 1/58 Ω·mm²/m at 20 °C)
  4. IEC 60228:2023, Conductors of insulated cables (metric nominal cross-sections)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.