1.5 mm² Wire: Resistance, Diameter, AWG

Metric Wire Sizes

A 1.5 mm² copper conductor (IEC 60228) may have at most 12.1 Ω/km (3.6881 Ω/1000 ft) DC resistance at 20 °C as a solid or stranded conductor (class 1 or 2), or 13.3 Ω/km (4.0538 Ω/1000 ft) as a flexible conductor (class 5). A solid round conductor of this area is 1.38 mm (0.0543 in) in diameter. The nearest AWG size is 16 AWG.

SNominal cross-section
1.5 mm²
RMax. resistance, class 1/2 (solid, stranded)
12.1 Ω/km3.6881 Ω/1000 ft3.6881 Ω/1000 ft12.1 Ω/km
RMax. resistance, class 5 (flexible)
13.3 Ω/km4.0538 Ω/1000 ft4.0538 Ω/1000 ft13.3 Ω/km
Nearest AWG
16 AWG

Drawing

⌀1.38 mm⌀0.0543 in1.5 mm²Solid round conductor, nominal area
1.5 mm² / 16 AWG16 AWG: 1.31 mm² (-13 %)
Left: solid round conductor of the nominal area. Right: the same with the nearest AWG / kcmil size overlaid (orange).Drawn to scale · Dimensions in mmDimensions in inches

1.5 mm² specifications

SNominal cross-section1.5 mm²
dSolid conductor diameter (calc.)1.38 mm0.0543 in
Area in kcmil2.96 kcmil
RMax. resistance, class 1/2 (solid, stranded)12.1 Ω/km3.6881 Ω/1000 ft
RMax. resistance, class 5 (flexible)13.3 Ω/km4.0538 Ω/1000 ft
Nearest AWG16 AWG
Smallest AWG with at least this area14 AWG

1.5 mm² is the standard size for lighting circuits in most IEC countries, typically on a 10 A (or 16 A) breaker depending on country and installation method. It is slightly larger than 16 AWG (1.31 mm²) and smaller than 14 AWG (2.08 mm²).

Comparable AWG sizes

All Metric Wire Sizes sizes

Compare all 19 sizes in the Metric Wire Sizes chart →

Sources

  1. IEC 60228:2023, Conductors of insulated cables (Tables 1, 2/4 and 5: class 1, 2 and 5 copper, maximum resistance at 20 °C)
  2. Lapp: T11 Conductor resistances and strand structure, metric (based on IEC/EN 60228)
  3. Bayka: Conductor resistance (IEC 60228 / VDE 0295)
  4. ASTM B258: AWG nominal diameters and areas (for the AWG comparison)

Values last checked against these sources on November 15, 2026. · How we check data