2 AWG Wire Size

AWG Wire Gauge

2 AWG solid wire is 0.2576 in (6.543 mm) in diameter, with a copper cross-section of 33.63 mm² (66,370 circular mils). Solid annealed copper of this size has a DC resistance of 0.5127 Ω/km (0.1563 Ω/1000 ft) at 20 °C.

dDiameter
6.543 mm0.2576 in0.2576 in6.543 mm
ACross-section
33.63 mm²
RDC resistance, copper 20 °C
0.5127 Ω/km
Ampacity 75 °C (NEC)
115 A

Drawing

⌀6.543 mm⌀0.2576 inSolid33.63 mm²
⌀7.419 mm⌀0.2921 in7 × ⌀2.473 mm⌀0.0974 in7 strands, same area
Bare conductor without insulation; 7-strand shown as an uncompressed concentric lay.Drawn to scale · Dimensions in mmDimensions in inches

2 AWG specifications

dDiameter0.2576 in6.543 mm
ACross-section33.63 mm²
Circular mils66,370
RDC resistance, copper 20 °C0.5127 Ω/km
RDC resistance, copper 20 °C0.1563 Ω/1000 ft
Ampacity 60 °C (NEC)95 A
Ampacity 75 °C (NEC)115 A
Ampacity 90 °C (NEC)130 A
Next metric size up35 mm²

2 AWG copper carries 115 A at 75 °C, typical for 100 A sub-panel feeders and for heavy battery cables.

Also known as

#2

Metric (IEC 60228) size with at least the same area

All AWG Wire Gauge sizes

Compare all 44 sizes in the AWG Wire Gauge chart →

Sources

  1. ASTM B258: Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors
  2. NFPA 70, National Electrical Code (2023), Table 310.16: Ampacities of insulated conductors, 60/75/90 °C
  3. IEC 60028:1925, International standard of resistance for copper (annealed copper: 1/58 Ω·mm²/m at 20 °C)
  4. IEC 60228:2023, Conductors of insulated cables (metric nominal cross-sections)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.