35 mm² Wire: Resistance, Diameter, AWG
Metric Wire Sizes
A 35 mm² copper conductor (IEC 60228) may have at most 0.524 Ω/km (0.1597 Ω/1000 ft) DC resistance at 20 °C as a solid or stranded conductor (class 1 or 2), or 0.554 Ω/km (0.1689 Ω/1000 ft) as a flexible conductor (class 5). A solid round conductor of this area is 6.68 mm (0.2630 in) in diameter. The nearest AWG size is 2 AWG.
- SNominal cross-section
- 35 mm²
- RMax. resistance, class 1/2 (solid, stranded)
- 0.524 Ω/km0.1597 Ω/1000 ft0.1597 Ω/1000 ft0.524 Ω/km
- RMax. resistance, class 5 (flexible)
- 0.554 Ω/km0.1689 Ω/1000 ft0.1689 Ω/1000 ft0.554 Ω/km
- Nearest AWG
- 2 AWG
Drawing
35 mm² specifications
| SNominal cross-section | 35 mm² |
|---|---|
| dSolid conductor diameter (calc.) | 6.68 mm0.2630 in |
| Area in kcmil | 69.1 kcmil |
| RMax. resistance, class 1/2 (solid, stranded) | 0.524 Ω/km0.1597 Ω/1000 ft |
| RMax. resistance, class 5 (flexible) | 0.554 Ω/km0.1689 Ω/1000 ft |
| Nearest AWG | 2 AWG |
| Smallest AWG with at least this area | 1 AWG |
Comparable AWG sizes
All Metric Wire Sizes sizes
Sources
- IEC 60228:2023, Conductors of insulated cables (Tables 1, 2/4 and 5: class 1, 2 and 5 copper, maximum resistance at 20 °C)
- Lapp: T11 Conductor resistances and strand structure, metric (based on IEC/EN 60228)
- Bayka: Conductor resistance (IEC 60228 / VDE 0295)
- ASTM B258: AWG nominal diameters and areas (for the AWG comparison)
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.