20 AWG Wire Size

AWG Wire Gauge

20 AWG solid wire is 0.0320 in (0.813 mm) in diameter, with a copper cross-section of 0.5176 mm² (1,022 circular mils). Solid annealed copper of this size has a DC resistance of 33.31 Ω/km (10.15 Ω/1000 ft) at 20 °C.

dDiameter
0.813 mm0.0320 in0.0320 in0.813 mm
ACross-section
0.5176 mm²
RDC resistance, copper 20 °C
33.31 Ω/km

Drawing

⌀0.813 mm⌀0.0320 inSolid0.5176 mm²
⌀0.922 mm⌀0.0363 in7 × ⌀0.307 mm⌀0.0121 in7 strands, same area
Bare conductor without insulation; 7-strand shown as an uncompressed concentric lay.Drawn to scale · Dimensions in mmDimensions in inches

20 AWG specifications

dDiameter0.0320 in0.813 mm
ACross-section0.5176 mm²
Circular mils1,022
RDC resistance, copper 20 °C33.31 Ω/km
RDC resistance, copper 20 °C10.15 Ω/1000 ft
Next metric size up0.75 mm²

20 AWG is close to 0.5 mm² and is used for hookup wire, small DC power leads and sensor cables.

Also known as

#20

Metric (IEC 60228) size with at least the same area

All AWG Wire Gauge sizes

Compare all 44 sizes in the AWG Wire Gauge chart →

Sources

  1. ASTM B258: Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors
  2. NFPA 70, National Electrical Code (2023), Table 310.16: Ampacities of insulated conductors, 60/75/90 °C
  3. IEC 60028:1925, International standard of resistance for copper (annealed copper: 1/58 Ω·mm²/m at 20 °C)
  4. IEC 60228:2023, Conductors of insulated cables (metric nominal cross-sections)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.