6 AWG Wire Size
AWG Wire Gauge
6 AWG solid wire is 0.1620 in (4.115 mm) in diameter, with a copper cross-section of 13.3 mm² (26,250 circular mils). Solid annealed copper of this size has a DC resistance of 1.296 Ω/km (0.3951 Ω/1000 ft) at 20 °C.
- dDiameter
- 4.115 mm0.1620 in0.1620 in4.115 mm
- ACross-section
- 13.3 mm²
- RDC resistance, copper 20 °C
- 1.296 Ω/km
- Ampacity 75 °C (NEC)
- 65 A
Drawing
6 AWG specifications
| dDiameter | 0.1620 in4.115 mm |
|---|---|
| ACross-section | 13.3 mm² |
| Circular mils | 26,250 |
| RDC resistance, copper 20 °C | 1.296 Ω/km |
| RDC resistance, copper 20 °C | 0.3951 Ω/1000 ft |
| Ampacity 60 °C (NEC) | 55 A |
| Ampacity 75 °C (NEC) | 65 A |
| Ampacity 90 °C (NEC) | 75 A |
| Next metric size up | 16 mm² |
6 AWG copper is used for 55–65 A feeds such as EV chargers on a 60 A breaker (with 75 °C terminations), subpanels and electric ranges.
Also known as
#6
Metric (IEC 60228) size with at least the same area
All AWG Wire Gauge sizes
Sources
- ASTM B258: Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors
- NFPA 70, National Electrical Code (2023), Table 310.16: Ampacities of insulated conductors, 60/75/90 °C
- IEC 60028:1925, International standard of resistance for copper (annealed copper: 1/58 Ω·mm²/m at 20 °C)
- IEC 60228:2023, Conductors of insulated cables (metric nominal cross-sections)
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.