16 mm² Wire: Resistance, Diameter, AWG

Metric Wire Sizes

A 16 mm² copper conductor (IEC 60228) may have at most 1.15 Ω/km (0.3505 Ω/1000 ft) DC resistance at 20 °C as a solid or stranded conductor (class 1 or 2), or 1.21 Ω/km (0.3688 Ω/1000 ft) as a flexible conductor (class 5). A solid round conductor of this area is 4.51 mm (0.1776 in) in diameter. The nearest AWG size is 6 AWG.

SNominal cross-section
16 mm²
RMax. resistance, class 1/2 (solid, stranded)
1.15 Ω/km0.3505 Ω/1000 ft0.3505 Ω/1000 ft1.15 Ω/km
RMax. resistance, class 5 (flexible)
1.21 Ω/km0.3688 Ω/1000 ft0.3688 Ω/1000 ft1.21 Ω/km
Nearest AWG
6 AWG

Drawing

⌀4.51 mm⌀0.1776 in16 mm²Solid round conductor, nominal area
16 mm² / 6 AWG6 AWG: 13.3 mm² (-17 %)
Left: solid round conductor of the nominal area. Right: the same with the nearest AWG / kcmil size overlaid (orange).Drawn to scale · Dimensions in mmDimensions in inches

16 mm² specifications

SNominal cross-section16 mm²
dSolid conductor diameter (calc.)4.51 mm0.1776 in
Area in kcmil31.6 kcmil
RMax. resistance, class 1/2 (solid, stranded)1.15 Ω/km0.3505 Ω/1000 ft
RMax. resistance, class 5 (flexible)1.21 Ω/km0.3688 Ω/1000 ft
Nearest AWG6 AWG
Smallest AWG with at least this area4 AWG

Comparable AWG sizes

All Metric Wire Sizes sizes

Compare all 19 sizes in the Metric Wire Sizes chart →

Sources

  1. IEC 60228:2023, Conductors of insulated cables (Tables 1, 2/4 and 5: class 1, 2 and 5 copper, maximum resistance at 20 °C)
  2. Lapp: T11 Conductor resistances and strand structure, metric (based on IEC/EN 60228)
  3. Bayka: Conductor resistance (IEC 60228 / VDE 0295)
  4. ASTM B258: AWG nominal diameters and areas (for the AWG comparison)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.