3-1/2" FMC Conduit Dimensions & Fill

Conduit Sizes · FMC: flexible metal conduit

3-1/2" FMC conduit has a nominal inside diameter of 3.500 in (88.9 mm) and a total inside area of 9.621 in² (6,207 mm²). NEC Chapter 9 allows 3.848 in² (2483 mm²) for three or more conductors (40 %), 2.983 in² (1925 mm²) for two and 5.099 in² (3290 mm²) for one.

IDInside diameter (nominal)
88.9 mm3.500 in3.500 in88.9 mm
A₄₀Fill area, over 2 wires (40 %)
2483 mm²3.848 in²3.848 in²2483 mm²

Drawing

40 % fill areaID ⌀88.9 mmID ⌀3.500 in
Bore and 40 % fill area to scale; the wall is drawn nominally because ENT/FMC outside diameters vary by maker.Proportions shown, not to scale · Dimensions in mmDimensions in inches

3-1/2" FMC specifications

Metric designator91
IDInside diameter (nominal)3.500 in88.9 mm
ATotal inside area (100 %)9.621 in²6,207 mm²
A₄₀Fill area, over 2 wires (40 %)3.848 in²2483 mm²
A₃₁Fill area, 2 wires (31 %)2.983 in²1925 mm²
A₅₃Fill area, 1 wire (53 %)5.099 in²3290 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.