3-1/2" EMT Conduit Dimensions & Fill
Conduit Sizes · EMT: electrical metallic tubing
3-1/2" EMT conduit has a nominal inside diameter of 3.834 in (97.4 mm) and a total inside area of 11.545 in² (7,448 mm²). NEC Chapter 9 allows 4.618 in² (2979 mm²) for three or more conductors (40 %), 3.579 in² (2309 mm²) for two and 6.119 in² (3948 mm²) for one.
- IDInside diameter (nominal)
- 97.4 mm3.834 in3.834 in97.4 mm
- ODOutside diameter
- 101.6 mm4.000 in4.000 in101.6 mm
- A₄₀Fill area, over 2 wires (40 %)
- 2979 mm²4.618 in²4.618 in²2979 mm²
Drawing
3-1/2" EMT specifications
| Metric designator | 91 |
|---|---|
| ODOutside diameter | 4.000 in101.6 mm |
| IDInside diameter (nominal) | 3.834 in97.4 mm |
| ATotal inside area (100 %) | 11.545 in²7,448 mm² |
| A₄₀Fill area, over 2 wires (40 %) | 4.618 in²2979 mm² |
| A₃₁Fill area, 2 wires (31 %) | 3.579 in²2309 mm² |
| A₅₃Fill area, 1 wire (53 %) | 6.119 in²3948 mm² |
Same trade size, other conduit types
All Conduit Sizes sizes
Sources
- NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
- NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
- Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
- Steel Tube Institute: Intermediate metal conduit
- PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
- IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.