3/8" FMC Conduit Dimensions & Fill

Conduit Sizes · FMC: flexible metal conduit

3/8" FMC conduit has a nominal inside diameter of 0.384 in (9.8 mm) and a total inside area of 0.116 in² (75 mm²). NEC Chapter 9 allows 0.046 in² (30 mm²) for three or more conductors (40 %), 0.036 in² (23 mm²) for two and 0.061 in² (39 mm²) for one.

IDInside diameter (nominal)
9.8 mm0.384 in0.384 in9.8 mm
A₄₀Fill area, over 2 wires (40 %)
30 mm²0.046 in²0.046 in²30 mm²

Drawing

40 % fill areaID ⌀9.8 mmID ⌀0.384 in
Bore and 40 % fill area to scale; the wall is drawn nominally because ENT/FMC outside diameters vary by maker.Proportions shown, not to scale · Dimensions in mmDimensions in inches

3/8" FMC specifications

Metric designator12
IDInside diameter (nominal)0.384 in9.8 mm
ATotal inside area (100 %)0.116 in²75 mm²
A₄₀Fill area, over 2 wires (40 %)0.046 in²30 mm²
A₃₁Fill area, 2 wires (31 %)0.036 in²23 mm²
A₅₃Fill area, 1 wire (53 %)0.061 in²39 mm²

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.