1/2" FMC Conduit Dimensions & Fill
Conduit Sizes · FMC: flexible metal conduit
1/2" FMC conduit has a nominal inside diameter of 0.635 in (16.1 mm) and a total inside area of 0.317 in² (205 mm²). NEC Chapter 9 allows 0.127 in² (82 mm²) for three or more conductors (40 %), 0.098 in² (63 mm²) for two and 0.168 in² (108 mm²) for one.
- IDInside diameter (nominal)
- 16.1 mm0.635 in0.635 in16.1 mm
- A₄₀Fill area, over 2 wires (40 %)
- 82 mm²0.127 in²0.127 in²82 mm²
Drawing
1/2" FMC specifications
| Metric designator | 16 |
|---|---|
| IDInside diameter (nominal) | 0.635 in16.1 mm |
| ATotal inside area (100 %) | 0.317 in²205 mm² |
| A₄₀Fill area, over 2 wires (40 %) | 0.127 in²82 mm² |
| A₃₁Fill area, 2 wires (31 %) | 0.098 in²63 mm² |
| A₅₃Fill area, 1 wire (53 %) | 0.168 in²108 mm² |
Same trade size, other conduit types
All Conduit Sizes sizes
Sources
- NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
- NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
- Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
- Steel Tube Institute: Intermediate metal conduit
- PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
- IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.