6" PVC Sch 40 Conduit Dimensions & Fill
Conduit Sizes · PVC Schedule 40
6" PVC Sch 40 conduit has a nominal inside diameter of 6.031 in (153.2 mm) and a total inside area of 28.567 in² (18,430 mm²). NEC Chapter 9 allows 11.427 in² (7372 mm²) for three or more conductors (40 %), 8.856 in² (5714 mm²) for two and 15.141 in² (9768 mm²) for one.
- IDInside diameter (nominal)
- 153.2 mm6.031 in6.031 in153.2 mm
- ODOutside diameter
- 168.3 mm6.625 in6.625 in168.3 mm
- A₄₀Fill area, over 2 wires (40 %)
- 7372 mm²11.427 in²11.427 in²7372 mm²
Drawing
6" PVC Sch 40 specifications
| Metric designator | 155 |
|---|---|
| ODOutside diameter | 6.625 in168.3 mm |
| IDInside diameter (nominal) | 6.031 in153.2 mm |
| ATotal inside area (100 %) | 28.567 in²18,430 mm² |
| A₄₀Fill area, over 2 wires (40 %) | 11.427 in²7372 mm² |
| A₃₁Fill area, 2 wires (31 %) | 8.856 in²5714 mm² |
| A₅₃Fill area, 1 wire (53 %) | 15.141 in²9768 mm² |
Same trade size, other conduit types
All Conduit Sizes sizes
Sources
- NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
- NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
- Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
- Steel Tube Institute: Intermediate metal conduit
- PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
- IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads
Values last checked against these sources on November 15, 2026. · How we check data