5" PVC Sch 40 Conduit Dimensions & Fill

Conduit Sizes · PVC Schedule 40

5" PVC Sch 40 conduit has a nominal inside diameter of 5.016 in (127.4 mm) and a total inside area of 19.761 in² (12,749 mm²). NEC Chapter 9 allows 7.904 in² (5099 mm²) for three or more conductors (40 %), 6.126 in² (3952 mm²) for two and 10.473 in² (6757 mm²) for one.

IDInside diameter (nominal)
127.4 mm5.016 in5.016 in127.4 mm
ODOutside diameter
141.3 mm5.563 in5.563 in141.3 mm
A₄₀Fill area, over 2 wires (40 %)
5099 mm²7.904 in²7.904 in²5099 mm²

Drawing

40 % fill areaID ⌀127.4 mmID ⌀5.016 inOD ⌀141.3 mmOD ⌀5.563 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

5" PVC Sch 40 specifications

Metric designator129
ODOutside diameter5.563 in141.3 mm
IDInside diameter (nominal)5.016 in127.4 mm
ATotal inside area (100 %)19.761 in²12,749 mm²
A₄₀Fill area, over 2 wires (40 %)7.904 in²5099 mm²
A₃₁Fill area, 2 wires (31 %)6.126 in²3952 mm²
A₅₃Fill area, 1 wire (53 %)10.473 in²6757 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.