50 mm² Wire: Resistance, Diameter, AWG
Metric Wire Sizes
A 50 mm² copper conductor (IEC 60228) may have at most 0.387 Ω/km (0.1180 Ω/1000 ft) DC resistance at 20 °C as a solid or stranded conductor (class 1 or 2), or 0.386 Ω/km (0.1177 Ω/1000 ft) as a flexible conductor (class 5). A solid round conductor of this area is 7.98 mm (0.3142 in) in diameter. The nearest AWG size is 1/0 AWG.
- SNominal cross-section
- 50 mm²
- RMax. resistance, class 1/2 (solid, stranded)
- 0.387 Ω/km0.1180 Ω/1000 ft0.1180 Ω/1000 ft0.387 Ω/km
- RMax. resistance, class 5 (flexible)
- 0.386 Ω/km0.1177 Ω/1000 ft0.1177 Ω/1000 ft0.386 Ω/km
- Nearest AWG
- 1/0 AWG
Drawing
50 mm² specifications
| SNominal cross-section | 50 mm² |
|---|---|
| dSolid conductor diameter (calc.) | 7.98 mm0.3142 in |
| Area in kcmil | 98.7 kcmil |
| RMax. resistance, class 1/2 (solid, stranded) | 0.387 Ω/km0.1180 Ω/1000 ft |
| RMax. resistance, class 5 (flexible) | 0.386 Ω/km0.1177 Ω/1000 ft |
| Nearest AWG | 1/0 AWG |
| Smallest AWG with at least this area | 1/0 AWG |
50 mm² class 5 has a lower resistance limit (0.386 Ω/km) than class 2 (0.387 Ω/km). That is how IEC 60228 lists it, not a typo.
Comparable AWG sizes
All Metric Wire Sizes sizes
Sources
- IEC 60228:2023, Conductors of insulated cables (Tables 1, 2/4 and 5: class 1, 2 and 5 copper, maximum resistance at 20 °C)
- Lapp: T11 Conductor resistances and strand structure, metric (based on IEC/EN 60228)
- Bayka: Conductor resistance (IEC 60228 / VDE 0295)
- ASTM B258: AWG nominal diameters and areas (for the AWG comparison)
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.