Rack Unit Chart: 1U to 52U Height in Inches and mm

One rack unit is 1U = 1.75 in = 44.45 mm, so a 42U rack has 73.5 in (1866.9 mm) of mounting space. Front panels are made 1/32 in shorter than their nominal height (1U panel = 1.719 in, 43.66 mm) so stacked equipment does not bind, and every unit has three holes per rail.

52 heightsChecked 2026-11-156 sources
1U1U15.8755/8″15.8755/8″12.71/2″44.451.75″
482.6 mm19″465.1 mm18.312″450.85 mm17.75″clear opening
Rail: a 2U section to scale, unit boundaries as centre lines. Widths: panel, hole centres and clear opening (height schematic).Proportions shown, not to scale

Rack unit chartHeight of 1U to 52U

52 of 52
UnitsHHeightmminFront panel heightmminHoles per rail
1U44.451.7543.661.7193
2U88.903.588.113.4696
3U133.355.25132.565.2199
4U177.807177.016.96912
5U222.258.75221.468.71915
6U266.7010.5265.9110.46918
7U311.1512.25310.3612.21921
8U355.6014354.8113.96924
9U400.0515.75399.2615.71927
10U444.5017.5443.7117.46930
11U488.9519.25488.1619.21933
12U533.4021532.6120.96936
13U577.8522.75577.0622.71939
14U622.3024.5621.5124.46942
15U666.7526.25665.9626.21945
16U711.2028710.4127.96948
17U755.6529.75754.8629.71951
18U800.1031.5799.3131.46954
19U844.5533.25843.7633.21957
20U889.0035888.2134.96960
21U933.4536.75932.6636.71963
22U977.9038.5977.1138.46966
23U1022.3540.251021.5640.21969
24U1066.80421066.0141.96972
25U1111.2543.751110.4643.71975
26U1155.7045.51154.9145.46978
27U1200.1547.251199.3647.21981
28U1244.60491243.8148.96984
29U1289.0550.751288.2650.71987
30U1333.5052.51332.7152.46990
31U1377.9554.251377.1654.21993
32U1422.40561421.6155.96996
33U1466.8557.751466.0657.71999
34U1511.3059.51510.5159.469102
35U1555.7561.251554.9661.219105
36U1600.20631599.4162.969108
37U1644.6564.751643.8664.719111
38U1689.1066.51688.3166.469114
39U1733.5568.251732.7668.219117
40U1778.00701777.2169.969120
41U1822.4571.751821.6671.719123
42U1866.9073.51866.1173.469126
43U1911.3575.251910.5675.219129
44U1955.80771955.0176.969132
45U2000.2578.751999.4678.719135
46U2044.7080.52043.9180.469138
47U2089.1582.252088.3682.219141
48U2133.60842132.8183.969144
49U2178.0585.752177.2685.719147
50U2222.5087.52221.7187.469150
51U2266.9589.252266.1689.219153
52U2311.40912310.6190.969156

Counting units on a rail

The rail holes repeat every 1.75 in in a pattern of three: spacing 1/2 in, 5/8 in, 5/8 in (12.7, 15.875, 15.875 mm). The 1/2 in gap straddles the boundary between two units, so the closely spaced pair of holes marks where one U ends and the next begins. Many rails are also printed with unit numbers.

To measure equipment, divide its height by 1.75 in (44.45 mm) and round up: a device 3.4 in (86 mm) tall needs 2U. Panel heights in the chart are the maximum for a front panel of that size under EIA-310.

A rack's total height in U refers only to the usable mounting space. The outside of a 42U cabinet is typically about 2 m (78–80 in) tall with base, roof and casters, but this varies by maker.

About Rack Units (U)

The 19-inch rack is defined in the US by EIA-310 and internationally by IEC 60297-3-100, with the same basic sizes: front panels are 19 in (482.6 mm) wide, the mounting holes are 18.312 in (465.1 mm) apart centre to centre, and the clear opening between the rails is 17.75 in (450.85 mm, usually quoted as 450 mm). Equipment bodies must be narrower than the opening; rack ears carry the 19-inch panel.

Rails come with square holes for cage nuts (most server racks, usually M6 cage nuts), with round tapped holes (10-32 UNF or 12-24 in US audio and telecom racks, M6 in Europe), or with round unthreaded holes for clip nuts. Rack-mount servers mostly use tool-less rail kits that hook straight into square holes.

Depth is not set by EIA-310. Servers need deep cabinets (1000–1200 mm) with front and rear rails; network and AV equipment often fits 600 mm cabinets or two-post open racks. Wall-mount cabinets come in 4U to about 24U.

Common cabinet sizes

Typical sizes from rack makers; check the maker's data for the exact outside dimensions and the rail depth range.

CabinetTypical use
600 mm wide × 600 mm deepNetwork switches, patch panels, small wall cabinets
600 × 800 mmNetwork, short servers, AV
600 × 1000 mm / 600 × 1070 mmStandard server cabinets
600 × 1200 mmDeep servers, storage, GPU systems
800 mm wideNetwork cabinets with cable management at the sides
42U, 45U, 47U, 48UFull-height data centre cabinets

Related units

HP (horizontal pitch) = 0.2 in (5.08 mm) is the width unit of 19-inch subracks and Eurocard / Eurorack modules; a full 19-inch subrack holds 84 HP. Open Compute Project racks use the OpenU (OU) of 48 mm and a 21-inch equipment width; they are not interchangeable with EIA-310 rails.

Questions

How tall is 1U in mm?

44.45 mm (1.75 in). A 1U front panel is 43.66 mm (1.719 in), 1/32 in less, to leave a gap between stacked devices.

How many inches is a 42U rack?

42 × 1.75 = 73.5 in (1866.9 mm) of mounting space. The cabinet itself is taller, typically about 78–80 in (2 m) outside.

How wide is a 19-inch rack?

The front panel is 19 in (482.6 mm). The mounting holes are 18.312 in (465.1 mm) apart and the clear opening between the rails is 17.75 in (450.85 mm). Cabinets are usually 600 or 800 mm wide outside.

What is the hole spacing on a rack rail?

Three holes per unit, spaced 1/2 in, 5/8 in, 5/8 in (12.7, 15.875, 15.875 mm), repeating every 1.75 in. The 1/2 in pair sits across the boundary between two units.

How many U is a 2 m rack?

Usually 42U. Cabinets around 2.2 m tall hold 47U or 48U.

Sources

  1. EIA/ECA-310-E: Cabinets, Racks, Panels, and Associated Equipment (1U = 1.75 in, universal hole spacing)
  2. IEC 60297-3-100: Mechanical structures for electronic equipment: 482.6 mm (19 in) series, basic dimensions
  3. Middle Atlantic Products: Rack basics and EIA-310 dimensions (panel heights, hole pattern)
  4. Schneider Electric APC: What is a rack unit (U) and EIA-310 rack standards
  5. Rittal: 19-inch technology and IEC 60297 / EIA-310 basics
  6. Wikipedia: 19-inch rack (17.75 in opening, 18.28–18.34 in hole centres, panel height 1.75n − 0.031 in)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.