10 AWG Wire Size
AWG Wire Gauge
10 AWG solid wire is 0.1019 in (2.588 mm) in diameter, with a copper cross-section of 5.261 mm² (10,380 circular mils). Solid annealed copper of this size has a DC resistance of 3.277 Ω/km (0.9988 Ω/1000 ft) at 20 °C.
- dDiameter
- 2.588 mm0.1019 in0.1019 in2.588 mm
- ACross-section
- 5.261 mm²
- RDC resistance, copper 20 °C
- 3.277 Ω/km
- Ampacity 75 °C (NEC)
- 35 A
Drawing
10 AWG specifications
| dDiameter | 0.1019 in2.588 mm |
|---|---|
| ACross-section | 5.261 mm² |
| Circular mils | 10,380 |
| RDC resistance, copper 20 °C | 3.277 Ω/km |
| RDC resistance, copper 20 °C | 0.9988 Ω/1000 ft |
| Ampacity 60 °C (NEC) | 30 A |
| Ampacity 75 °C (NEC) | 35 A |
| Ampacity 90 °C (NEC) | 40 A |
| Next metric size up | 6 mm² |
10 AWG is used for 30 A circuits: electric water heaters, dryers (older three-wire), and many air-conditioning units. It is also common for 12 V and 24 V runs where voltage drop decides the size.
Also known as
#10
Metric (IEC 60228) size with at least the same area
All AWG Wire Gauge sizes
Sources
- ASTM B258: Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors
- NFPA 70, National Electrical Code (2023), Table 310.16: Ampacities of insulated conductors, 60/75/90 °C
- IEC 60028:1925, International standard of resistance for copper (annealed copper: 1/58 Ω·mm²/m at 20 °C)
- IEC 60228:2023, Conductors of insulated cables (metric nominal cross-sections)
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.