6 mm² Wire: Resistance, Diameter, AWG
Metric Wire Sizes
A 6 mm² copper conductor (IEC 60228) may have at most 3.08 Ω/km (0.9388 Ω/1000 ft) DC resistance at 20 °C as a solid or stranded conductor (class 1 or 2), or 3.3 Ω/km (1.0058 Ω/1000 ft) as a flexible conductor (class 5). A solid round conductor of this area is 2.76 mm (0.1087 in) in diameter. The nearest AWG size is 10 AWG.
- SNominal cross-section
- 6 mm²
- RMax. resistance, class 1/2 (solid, stranded)
- 3.08 Ω/km0.9388 Ω/1000 ft0.9388 Ω/1000 ft3.08 Ω/km
- RMax. resistance, class 5 (flexible)
- 3.3 Ω/km1.0058 Ω/1000 ft1.0058 Ω/1000 ft3.3 Ω/km
- Nearest AWG
- 10 AWG
Drawing
6 mm² specifications
| SNominal cross-section | 6 mm² |
|---|---|
| dSolid conductor diameter (calc.) | 2.76 mm0.1087 in |
| Area in kcmil | 11.8 kcmil |
| RMax. resistance, class 1/2 (solid, stranded) | 3.08 Ω/km0.9388 Ω/1000 ft |
| RMax. resistance, class 5 (flexible) | 3.3 Ω/km1.0058 Ω/1000 ft |
| Nearest AWG | 10 AWG |
| Smallest AWG with at least this area | 8 AWG |
6 mm² is typical for electric cookers and showers (32–40 A, depending on installation method) and for longer PV runs.
Comparable AWG sizes
All Metric Wire Sizes sizes
Sources
- IEC 60228:2023, Conductors of insulated cables (Tables 1, 2/4 and 5: class 1, 2 and 5 copper, maximum resistance at 20 °C)
- Lapp: T11 Conductor resistances and strand structure, metric (based on IEC/EN 60228)
- Bayka: Conductor resistance (IEC 60228 / VDE 0295)
- ASTM B258: AWG nominal diameters and areas (for the AWG comparison)
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.