4/0 AWG Wire Size
AWG Wire Gauge
4/0 AWG solid wire is 0.4600 in (11.684 mm) in diameter, with a copper cross-section of 107.2 mm² (211,600 circular mils). Solid annealed copper of this size has a DC resistance of 0.1608 Ω/km (0.049 Ω/1000 ft) at 20 °C.
- dDiameter
- 11.684 mm0.4600 in0.4600 in11.684 mm
- ACross-section
- 107.2 mm²
- RDC resistance, copper 20 °C
- 0.1608 Ω/km
- Ampacity 75 °C (NEC)
- 230 A
Drawing
4/0 AWG specifications
| dDiameter | 0.4600 in11.684 mm |
|---|---|
| ACross-section | 107.2 mm² |
| Circular mils | 211,600 |
| RDC resistance, copper 20 °C | 0.1608 Ω/km |
| RDC resistance, copper 20 °C | 0.049 Ω/1000 ft |
| Ampacity 60 °C (NEC) | 195 A |
| Ampacity 75 °C (NEC) | 230 A |
| Ampacity 90 °C (NEC) | 260 A |
| Next metric size up | 120 mm² |
4/0 (0000) is the largest AWG size; above it, cable is sized in kcmil (250, 300, 350 kcmil …). 4/0 copper is rated 230 A at 75 °C. Note that 4/0 aluminum (rated 180 A at 75 °C) is common for 200 A residential services under the NEC 310.12 dwelling service rule, which permits 83 % of the service rating.
Also known as
Metric (IEC 60228) size with at least the same area
All AWG Wire Gauge sizes
Sources
- ASTM B258: Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors
- NFPA 70, National Electrical Code (2023), Table 310.16: Ampacities of insulated conductors, 60/75/90 °C
- IEC 60028:1925, International standard of resistance for copper (annealed copper: 1/58 Ω·mm²/m at 20 °C)
- IEC 60228:2023, Conductors of insulated cables (metric nominal cross-sections)
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.