8 AWG Wire Size

AWG Wire Gauge

8 AWG solid wire is 0.1285 in (3.264 mm) in diameter, with a copper cross-section of 8.366 mm² (16,510 circular mils). Solid annealed copper of this size has a DC resistance of 2.061 Ω/km (0.6282 Ω/1000 ft) at 20 °C.

dDiameter
3.264 mm0.1285 in0.1285 in3.264 mm
ACross-section
8.366 mm²
RDC resistance, copper 20 °C
2.061 Ω/km
Ampacity 75 °C (NEC)
50 A

Drawing

⌀3.264 mm⌀0.1285 inSolid8.366 mm²
⌀3.701 mm⌀0.1457 in7 × ⌀1.234 mm⌀0.0486 in7 strands, same area
Bare conductor without insulation; 7-strand shown as an uncompressed concentric lay.Drawn to scale · Dimensions in mmDimensions in inches

8 AWG specifications

dDiameter0.1285 in3.264 mm
ACross-section8.366 mm²
Circular mils16,510
RDC resistance, copper 20 °C2.061 Ω/km
RDC resistance, copper 20 °C0.6282 Ω/1000 ft
Ampacity 60 °C (NEC)40 A
Ampacity 75 °C (NEC)50 A
Ampacity 90 °C (NEC)55 A
Next metric size up10 mm²

8 AWG copper is typical for 40 A circuits (ranges, cooktops) with 60 °C cable and for 50 A with 75 °C terminations and conductors.

Also known as

#8

Metric (IEC 60228) size with at least the same area

All AWG Wire Gauge sizes

Compare all 44 sizes in the AWG Wire Gauge chart →

Sources

  1. ASTM B258: Standard Specification for Standard Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors
  2. NFPA 70, National Electrical Code (2023), Table 310.16: Ampacities of insulated conductors, 60/75/90 °C
  3. IEC 60028:1925, International standard of resistance for copper (annealed copper: 1/58 Ω·mm²/m at 20 °C)
  4. IEC 60228:2023, Conductors of insulated cables (metric nominal cross-sections)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.