10 mm² Wire: Resistance, Diameter, AWG

Metric Wire Sizes

A 10 mm² copper conductor (IEC 60228) may have at most 1.83 Ω/km (0.5578 Ω/1000 ft) DC resistance at 20 °C as a solid or stranded conductor (class 1 or 2), or 1.91 Ω/km (0.5822 Ω/1000 ft) as a flexible conductor (class 5). A solid round conductor of this area is 3.57 mm (0.1406 in) in diameter. The nearest AWG size is 8 AWG.

SNominal cross-section
10 mm²
RMax. resistance, class 1/2 (solid, stranded)
1.83 Ω/km0.5578 Ω/1000 ft0.5578 Ω/1000 ft1.83 Ω/km
RMax. resistance, class 5 (flexible)
1.91 Ω/km0.5822 Ω/1000 ft0.5822 Ω/1000 ft1.91 Ω/km
Nearest AWG
8 AWG

Drawing

⌀3.57 mm⌀0.1406 in10 mm²Solid round conductor, nominal area
10 mm² / 8 AWG8 AWG: 8.37 mm² (-16 %)
Left: solid round conductor of the nominal area. Right: the same with the nearest AWG / kcmil size overlaid (orange).Drawn to scale · Dimensions in mmDimensions in inches

10 mm² specifications

SNominal cross-section10 mm²
dSolid conductor diameter (calc.)3.57 mm0.1406 in
Area in kcmil19.7 kcmil
RMax. resistance, class 1/2 (solid, stranded)1.83 Ω/km0.5578 Ω/1000 ft
RMax. resistance, class 5 (flexible)1.91 Ω/km0.5822 Ω/1000 ft
Nearest AWG8 AWG
Smallest AWG with at least this area6 AWG

10 mm² is common for sub-main feeds, EV chargers on longer runs and main protective bonding conductors.

Comparable AWG sizes

All Metric Wire Sizes sizes

Compare all 19 sizes in the Metric Wire Sizes chart →

Sources

  1. IEC 60228:2023, Conductors of insulated cables (Tables 1, 2/4 and 5: class 1, 2 and 5 copper, maximum resistance at 20 °C)
  2. Lapp: T11 Conductor resistances and strand structure, metric (based on IEC/EN 60228)
  3. Bayka: Conductor resistance (IEC 60228 / VDE 0295)
  4. ASTM B258: AWG nominal diameters and areas (for the AWG comparison)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.