PG9 Cable Gland Thread & Hole Size

Cable Glands · PG: steel conduit thread (DIN 40430)

A PG9 cable gland has a 15.2 mm (0.598 in) entry thread with 1.411 mm (18.0 TPI) pitch. The table below gives the clearance hole for a gland held by a locknut and the tap drill for a threaded entry.

dThread outside diameter
15.2 mm0.598 in0.598 in15.2 mm
PThread pitch
1.411 mm18.0 TPI18.0 TPI1.411 mm
⌀Clearance hole
15.4–15.7 mm0.606–0.618 in0.606–0.618 in15.4–15.7 mm

Drawing

⌀15.2 mm⌀0.598 inpitch 1.411 mm18.0 TPIhole ⌀15.4–15.7 mmhole ⌀0.606–0.618 inenclosure wall
Gland with locknut through an enclosure wall. Thread and hole proportional; body and cap nut shape typical.Proportions shown, not to scale · Dimensions in mmDimensions in inches

PG9 specifications

dThread outside diameter15.2 mm0.598 in
PThread pitch1.411 mm18.0 TPI
⌀Clearance hole15.4–15.7 mm0.606–0.618 in
Tap drill (threaded entry)14 mm0.551 in

All Cable Glands sizes

Compare all 24 thread sizes in the Cable Glands chart →

Sources

  1. DIN 40430: Steel conduit thread (PG): dimensions, via gewindebohrer.de thread tables
  2. Heyco: PG hub liquid-tight cordgrip, DIN 40430 thread specifications
  3. Newman Tools: PG steel conduit taps per DIN 40430 (tap drill sizes)
  4. LAPP: SKINTOP ST-M cable glands, metric (clamping ranges)
  5. metric-bolt-torque.com: Cable gland sizes and entry holes
  6. Greenlee: Standard round knockout punches (hole sizes per conduit trade size)
  7. ASME B1.20.1: Pipe threads, general purpose (inch), NPT

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.