MC Cable Wire and Cable Specifications

US Cable Types · Cable assemblies

MC Cable: Metal-Clad cable (interlocked aluminum or steel armor). Voltage rating 600 V. Conductor insulation rated up to 90°C (194°F). Listed for dry, damp locations. Covered by NEC Article 330; typical sizes 14 AWG – 1000 kcmil.

Voltage rating
600 V
Max. conductor temp.
90°C194°F194°F90°C
NEC article
330

Drawing

metal armor · insulation · solid conductor
Typical construction. Core colors are examples.Schematic, not to scale

MC Cable specifications

Meaning of the lettersMetal-Clad cable (interlocked aluminum or steel armor)
Voltage rating600 V
Max. conductor temp.90°C194°F
Locationsdry, damp
Conductor insulationPVC + nylon
Jacket / armormetal armor
NEC article330
Sizes14 AWG – 1000 kcmil

MC cable has an interlocking metal armor over THHN conductors and a separate insulated green grounding conductor. MC-AP (aluminum armor with a bare aluminum bonding wire) lets the armor serve as the equipment ground. Used where codes or specifications exclude NM cable (commercial buildings, exposed runs).

Other types in this group

All US Cable Types sizes

Compare all 16 sizes in the US Cable Types chart →

Sources

  1. NFPA 70, National Electrical Code (2023): Table 310.4(1); Articles 320, 330, 334, 336, 338, 340, 400, 402, 690
  2. Southwire: Romex SIMpull Type NM-B, spec 10028 (600 V, 90 °C conductors, 60 °C ampacity, jacket colour code)
  3. Southwire: Copper Service Entrance SER / SEU cable (XHHW-2, 90 °C wet or dry, grey PVC jacket)
  4. Southwire: RHH/RHW-2/USE-2 copper, spec 10010 (600 V, 90 °C wet or dry)
  5. UL 83 (thermoplastic insulated wires), UL 44 (thermoset), UL 719 (NM), UL 1569 (MC), UL 854 (SE/USE), UL 4703 (PV wire), UL 62 (flexible cords)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.