NM-B (Romex) Wire and Cable Specifications

US Cable Types · Cable assemblies

NM-B (Romex): Non-Metallic sheathed cable, B = 90 °C conductors. Voltage rating 600 V. Conductor insulation rated up to 90°C (194°F). Listed for dry locations. Covered by NEC Article 334; typical sizes 14 – 2 AWG Cu.

Voltage rating
600 V
Max. conductor temp.
90°C194°F194°F90°C
NEC article
334

Drawing

jacket · insulation · solid conductorbare ground
Typical construction. Core colors are examples.Schematic, not to scale

NM-B (Romex) specifications

Meaning of the lettersNon-Metallic sheathed cable, B = 90 °C conductors
Voltage rating600 V
Max. conductor temp.90°C194°F
Ampacity limited to60°C140°F
Locationsdry
Conductor insulationPVC + nylon
Jacket / armorPVC jacket
NEC article334
Sizes14 – 2 AWG Cu

NM-B is for dry locations only. The individual conductors are 90 °C THHN-type, but the cable's ampacity is limited to the 60 °C column (NEC 334.80): 14 AWG 15 A, 12 AWG 20 A, 10 AWG 30 A, 8 AWG 40 A, 6 AWG 55 A. Jacket color identifies the size (white 14, yellow 12, orange 10, black 8–6).

Other types in this group

All US Cable Types sizes

Compare all 16 sizes in the US Cable Types chart →

Sources

  1. NFPA 70, National Electrical Code (2023): Table 310.4(1); Articles 320, 330, 334, 336, 338, 340, 400, 402, 690
  2. Southwire: Romex SIMpull Type NM-B, spec 10028 (600 V, 90 °C conductors, 60 °C ampacity, jacket colour code)
  3. Southwire: Copper Service Entrance SER / SEU cable (XHHW-2, 90 °C wet or dry, grey PVC jacket)
  4. Southwire: RHH/RHW-2/USE-2 copper, spec 10010 (600 V, 90 °C wet or dry)
  5. UL 83 (thermoplastic insulated wires), UL 44 (thermoset), UL 719 (NM), UL 1569 (MC), UL 854 (SE/USE), UL 4703 (PV wire), UL 62 (flexible cords)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.