SEU Wire and Cable Specifications
US Cable Types · Cable assemblies
SEU: Service Entrance cable, style U (concentric bare neutral). Voltage rating 600 V. Conductor insulation rated up to 90°C (194°F). Listed for dry, wet, sunlight-resistant locations. Covered by NEC Article 338; typical sizes 8 AWG – 4/0 AWG Cu.
- Voltage rating
- 600 V
- Max. conductor temp.
- 90°C194°F194°F90°C
- NEC article
- 338
Drawing
SEU specifications
| Meaning of the letters | Service Entrance cable, style U (concentric bare neutral) |
|---|---|
| Voltage rating | 600 V |
| Max. conductor temp. | 90°C194°F |
| Locations | dry, wet, sunlight-resistant |
| Conductor insulation | XLPE (cross-linked PE) |
| Jacket / armor | PVC jacket |
| NEC article | 338 |
| Sizes | 8 AWG – 4/0 AWG Cu |
SEU has two insulated conductors and a bare concentric neutral wound around them, under a gray jacket. Used for overhead service drops to the meter and from meter to the service panel, not for feeders where the neutral must be insulated.
Other types in this group
All US Cable Types sizes
Sources
- NFPA 70, National Electrical Code (2023): Table 310.4(1); Articles 320, 330, 334, 336, 338, 340, 400, 402, 690
- Southwire: Romex SIMpull Type NM-B, spec 10028 (600 V, 90 °C conductors, 60 °C ampacity, jacket colour code)
- Southwire: Copper Service Entrance SER / SEU cable (XHHW-2, 90 °C wet or dry, grey PVC jacket)
- Southwire: RHH/RHW-2/USE-2 copper, spec 10010 (600 V, 90 °C wet or dry)
- UL 83 (thermoplastic insulated wires), UL 44 (thermoset), UL 719 (NM), UL 1569 (MC), UL 854 (SE/USE), UL 4703 (PV wire), UL 62 (flexible cords)
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.