SEU Wire and Cable Specifications

US Cable Types · Cable assemblies

SEU: Service Entrance cable, style U (concentric bare neutral). Voltage rating 600 V. Conductor insulation rated up to 90°C (194°F). Listed for dry, wet, sunlight-resistant locations. Covered by NEC Article 338; typical sizes 8 AWG – 4/0 AWG Cu.

Voltage rating
600 V
Max. conductor temp.
90°C194°F194°F90°C
NEC article
338

Drawing

jacket · concentric neutral · insulationstranded conductor
Typical construction. Core colors are examples.Schematic, not to scale

SEU specifications

Meaning of the lettersService Entrance cable, style U (concentric bare neutral)
Voltage rating600 V
Max. conductor temp.90°C194°F
Locationsdry, wet, sunlight-resistant
Conductor insulationXLPE (cross-linked PE)
Jacket / armorPVC jacket
NEC article338
Sizes8 AWG – 4/0 AWG Cu

SEU has two insulated conductors and a bare concentric neutral wound around them, under a gray jacket. Used for overhead service drops to the meter and from meter to the service panel, not for feeders where the neutral must be insulated.

Other types in this group

All US Cable Types sizes

Compare all 16 sizes in the US Cable Types chart →

Sources

  1. NFPA 70, National Electrical Code (2023): Table 310.4(1); Articles 320, 330, 334, 336, 338, 340, 400, 402, 690
  2. Southwire: Romex SIMpull Type NM-B, spec 10028 (600 V, 90 °C conductors, 60 °C ampacity, jacket colour code)
  3. Southwire: Copper Service Entrance SER / SEU cable (XHHW-2, 90 °C wet or dry, grey PVC jacket)
  4. Southwire: RHH/RHW-2/USE-2 copper, spec 10010 (600 V, 90 °C wet or dry)
  5. UL 83 (thermoplastic insulated wires), UL 44 (thermoset), UL 719 (NM), UL 1569 (MC), UL 854 (SE/USE), UL 4703 (PV wire), UL 62 (flexible cords)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.