PV Wire Wire and Cable Specifications
US Cable Types · Single conductors (building wire)
PV Wire: Photovoltaic wire (UL 4703). Voltage rating 600 / 1000 / 2000 V. Conductor insulation rated up to 90°C (194°F). Listed for dry, wet, direct burial, sunlight-resistant locations. Covered by NEC Article 690; typical sizes 18 AWG – 1000 kcmil.
- Voltage rating
- 600 / 1000 / 2000 V
- Max. conductor temp.
- 90°C194°F194°F90°C
- NEC article
- 690
Drawing
PV Wire specifications
| Meaning of the letters | Photovoltaic wire (UL 4703) |
|---|---|
| Voltage rating | 600 / 1000 / 2000 V |
| Max. conductor temp. | 90°C194°F |
| Locations | dry, wet, direct burial, sunlight-resistant |
| Conductor insulation | XLPE (cross-linked PE) |
| NEC article | 690 |
| Sizes | 18 AWG – 1000 kcmil |
PV wire (UL 4703) is required for exposed single-conductor array wiring on ungrounded (transformerless) PV systems (NEC 690.31). It has a thicker insulation than USE-2 and is sunlight-resistant and wet-rated. The voltage rating (600, 1000 or 2000 V) is printed on the cable.
Other types in this group
All US Cable Types sizes
Sources
- NFPA 70, National Electrical Code (2023): Table 310.4(1); Articles 320, 330, 334, 336, 338, 340, 400, 402, 690
- Southwire: Romex SIMpull Type NM-B, spec 10028 (600 V, 90 °C conductors, 60 °C ampacity, jacket colour code)
- Southwire: Copper Service Entrance SER / SEU cable (XHHW-2, 90 °C wet or dry, grey PVC jacket)
- Southwire: RHH/RHW-2/USE-2 copper, spec 10010 (600 V, 90 °C wet or dry)
- UL 83 (thermoplastic insulated wires), UL 44 (thermoset), UL 719 (NM), UL 1569 (MC), UL 854 (SE/USE), UL 4703 (PV wire), UL 62 (flexible cords)
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.