PV Wire Wire and Cable Specifications

US Cable Types · Single conductors (building wire)

PV Wire: Photovoltaic wire (UL 4703). Voltage rating 600 / 1000 / 2000 V. Conductor insulation rated up to 90°C (194°F). Listed for dry, wet, direct burial, sunlight-resistant locations. Covered by NEC Article 690; typical sizes 18 AWG – 1000 kcmil.

Voltage rating
600 / 1000 / 2000 V
Max. conductor temp.
90°C194°F194°F90°C
NEC article
690

Drawing

insulation · stranded conductor
Typical construction. Core colors are examples.Schematic, not to scale

PV Wire specifications

Meaning of the lettersPhotovoltaic wire (UL 4703)
Voltage rating600 / 1000 / 2000 V
Max. conductor temp.90°C194°F
Locationsdry, wet, direct burial, sunlight-resistant
Conductor insulationXLPE (cross-linked PE)
NEC article690
Sizes18 AWG – 1000 kcmil

PV wire (UL 4703) is required for exposed single-conductor array wiring on ungrounded (transformerless) PV systems (NEC 690.31). It has a thicker insulation than USE-2 and is sunlight-resistant and wet-rated. The voltage rating (600, 1000 or 2000 V) is printed on the cable.

Other types in this group

All US Cable Types sizes

Compare all 16 sizes in the US Cable Types chart →

Sources

  1. NFPA 70, National Electrical Code (2023): Table 310.4(1); Articles 320, 330, 334, 336, 338, 340, 400, 402, 690
  2. Southwire: Romex SIMpull Type NM-B, spec 10028 (600 V, 90 °C conductors, 60 °C ampacity, jacket colour code)
  3. Southwire: Copper Service Entrance SER / SEU cable (XHHW-2, 90 °C wet or dry, grey PVC jacket)
  4. Southwire: RHH/RHW-2/USE-2 copper, spec 10010 (600 V, 90 °C wet or dry)
  5. UL 83 (thermoplastic insulated wires), UL 44 (thermoset), UL 719 (NM), UL 1569 (MC), UL 854 (SE/USE), UL 4703 (PV wire), UL 62 (flexible cords)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.