XHHW-2 Wire and Cable Specifications

US Cable Types · Single conductors (building wire)

XHHW-2: Cross-linked (X) High Heat-resistant, Water-resistant, 90 °C wet. Voltage rating 600 V. Conductor insulation rated up to 90°C (194°F). Listed for dry, damp, wet locations. Covered by NEC Article 310; typical sizes 14 AWG – 1000 kcmil.

Voltage rating
600 V
Max. conductor temp.
90°C194°F194°F90°C
NEC article
310

Drawing

insulation · stranded conductor
Typical construction. Core colors are examples.Schematic, not to scale

XHHW-2 specifications

Meaning of the lettersCross-linked (X) High Heat-resistant, Water-resistant, 90 °C wet
Voltage rating600 V
Max. conductor temp.90°C194°F
Locationsdry, damp, wet
Conductor insulationXLPE (cross-linked PE)
NEC article310
Sizes14 AWG – 1000 kcmil

XHHW-2 has a single tough XLPE insulation without a nylon jacket. It is slightly larger in diameter than THHN of the same size (conduit fill tables list it separately) and is the standard insulation for aluminum feeders and the conductors of SER cable.

Other types in this group

All US Cable Types sizes

Compare all 16 sizes in the US Cable Types chart →

Sources

  1. NFPA 70, National Electrical Code (2023): Table 310.4(1); Articles 320, 330, 334, 336, 338, 340, 400, 402, 690
  2. Southwire: Romex SIMpull Type NM-B, spec 10028 (600 V, 90 °C conductors, 60 °C ampacity, jacket colour code)
  3. Southwire: Copper Service Entrance SER / SEU cable (XHHW-2, 90 °C wet or dry, grey PVC jacket)
  4. Southwire: RHH/RHW-2/USE-2 copper, spec 10010 (600 V, 90 °C wet or dry)
  5. UL 83 (thermoplastic insulated wires), UL 44 (thermoset), UL 719 (NM), UL 1569 (MC), UL 854 (SE/USE), UL 4703 (PV wire), UL 62 (flexible cords)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.