THHN Wire and Cable Specifications

US Cable Types · Single conductors (building wire)

THHN: Thermoplastic, High Heat-resistant, Nylon-coated. Voltage rating 600 V. Conductor insulation rated up to 90°C (194°F). Listed for dry, damp locations. Covered by NEC Article 310; typical sizes 14 AWG – 1000 kcmil.

Voltage rating
600 V
Max. conductor temp.
90°C194°F194°F90°C
NEC article
310

Drawing

nylon jacket · insulation · stranded conductor
Typical construction. Core colors are examples.Schematic, not to scale

THHN specifications

Meaning of the lettersThermoplastic, High Heat-resistant, Nylon-coated
Voltage rating600 V
Max. conductor temp.90°C194°F
Locationsdry, damp
Conductor insulationPVC + nylon
NEC article310
Sizes14 AWG – 1000 kcmil

Plain THHN is rated 90 °C in dry and damp locations only. Nearly all THHN sold today is dual-listed THHN/THWN-2 and may also be used in wet locations (outdoor and underground conduit) at 90 °C. The nylon skin must be intact; nicked nylon is a common pulling defect.

Other types in this group

All US Cable Types sizes

Compare all 16 sizes in the US Cable Types chart →

Sources

  1. NFPA 70, National Electrical Code (2023): Table 310.4(1); Articles 320, 330, 334, 336, 338, 340, 400, 402, 690
  2. Southwire: Romex SIMpull Type NM-B, spec 10028 (600 V, 90 °C conductors, 60 °C ampacity, jacket colour code)
  3. Southwire: Copper Service Entrance SER / SEU cable (XHHW-2, 90 °C wet or dry, grey PVC jacket)
  4. Southwire: RHH/RHW-2/USE-2 copper, spec 10010 (600 V, 90 °C wet or dry)
  5. UL 83 (thermoplastic insulated wires), UL 44 (thermoset), UL 719 (NM), UL 1569 (MC), UL 854 (SE/USE), UL 4703 (PV wire), UL 62 (flexible cords)

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.