3" EMT conduit has a nominal inside diameter of 3.356 in (85.2 mm) and a total inside area of 8.846 in² (5,707 mm²). NEC Chapter 9 allows 3.538 in² (2283 mm²) for three or more conductors (40 %), 2.742 in² (1769 mm²) for two and 4.688 in² (3025 mm²) for one.

IDInside diameter (nominal)
85.2 mm3.356 in3.356 in85.2 mm
ODOutside diameter
88.9 mm3.500 in3.500 in88.9 mm
A₄₀Fill area, over 2 wires (40 %)
2283 mm²3.538 in²3.538 in²2283 mm²

Drawing

40 % fill areaID ⌀85.2 mmID ⌀3.356 inOD ⌀88.9 mmOD ⌀3.500 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

3" EMT specifications

Metric designator78
ODOutside diameter3.500 in88.9 mm
IDInside diameter (nominal)3.356 in85.2 mm
ATotal inside area (100 %)8.846 in²5,707 mm²
A₄₀Fill area, over 2 wires (40 %)3.538 in²2283 mm²
A₃₁Fill area, 2 wires (31 %)2.742 in²1769 mm²
A₅₃Fill area, 1 wire (53 %)4.688 in²3025 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.