4" IMC Conduit Dimensions & Fill

Conduit Sizes · IMC: intermediate metal conduit

4" IMC conduit has a nominal inside diameter of 4.166 in (105.8 mm) and a total inside area of 13.631 in² (8,794 mm²). NEC Chapter 9 allows 5.452 in² (3517 mm²) for three or more conductors (40 %), 4.226 in² (2726 mm²) for two and 7.224 in² (4661 mm²) for one.

IDInside diameter (nominal)
105.8 mm4.166 in4.166 in105.8 mm
ODOutside diameter
113.4 mm4.466 in4.466 in113.4 mm
A₄₀Fill area, over 2 wires (40 %)
3517 mm²5.452 in²5.452 in²3517 mm²

Drawing

40 % fill areaID ⌀105.8 mmID ⌀4.166 inOD ⌀113.4 mmOD ⌀4.466 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

4" IMC specifications

Metric designator103
ODOutside diameter4.466 in113.4 mm
IDInside diameter (nominal)4.166 in105.8 mm
ATotal inside area (100 %)13.631 in²8,794 mm²
A₄₀Fill area, over 2 wires (40 %)5.452 in²3517 mm²
A₃₁Fill area, 2 wires (31 %)4.226 in²2726 mm²
A₅₃Fill area, 1 wire (53 %)7.224 in²4661 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data