4" IMC Conduit Dimensions & Fill
Conduit Sizes · IMC: intermediate metal conduit
4" IMC conduit has a nominal inside diameter of 4.166 in (105.8 mm) and a total inside area of 13.631 in² (8,794 mm²). NEC Chapter 9 allows 5.452 in² (3517 mm²) for three or more conductors (40 %), 4.226 in² (2726 mm²) for two and 7.224 in² (4661 mm²) for one.
- IDInside diameter (nominal)
- 105.8 mm4.166 in4.166 in105.8 mm
- ODOutside diameter
- 113.4 mm4.466 in4.466 in113.4 mm
- A₄₀Fill area, over 2 wires (40 %)
- 3517 mm²5.452 in²5.452 in²3517 mm²
Drawing
4" IMC specifications
| Metric designator | 103 |
|---|---|
| ODOutside diameter | 4.466 in113.4 mm |
| IDInside diameter (nominal) | 4.166 in105.8 mm |
| ATotal inside area (100 %) | 13.631 in²8,794 mm² |
| A₄₀Fill area, over 2 wires (40 %) | 5.452 in²3517 mm² |
| A₃₁Fill area, 2 wires (31 %) | 4.226 in²2726 mm² |
| A₅₃Fill area, 1 wire (53 %) | 7.224 in²4661 mm² |
Same trade size, other conduit types
All Conduit Sizes sizes
Sources
- NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
- NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
- Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
- Steel Tube Institute: Intermediate metal conduit
- PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
- IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.