4" PVC Sch 40 Conduit Dimensions & Fill
Conduit Sizes · PVC Schedule 40
4" PVC Sch 40 conduit has a nominal inside diameter of 3.998 in (101.5 mm) and a total inside area of 12.554 in² (8,099 mm²). NEC Chapter 9 allows 5.022 in² (3240 mm²) for three or more conductors (40 %), 3.892 in² (2511 mm²) for two and 6.654 in² (4293 mm²) for one.
- IDInside diameter (nominal)
- 101.5 mm3.998 in3.998 in101.5 mm
- ODOutside diameter
- 114.3 mm4.500 in4.500 in114.3 mm
- A₄₀Fill area, over 2 wires (40 %)
- 3240 mm²5.022 in²5.022 in²3240 mm²
Drawing
4" PVC Sch 40 specifications
| Metric designator | 103 |
|---|---|
| ODOutside diameter | 4.500 in114.3 mm |
| IDInside diameter (nominal) | 3.998 in101.5 mm |
| ATotal inside area (100 %) | 12.554 in²8,099 mm² |
| A₄₀Fill area, over 2 wires (40 %) | 5.022 in²3240 mm² |
| A₃₁Fill area, 2 wires (31 %) | 3.892 in²2511 mm² |
| A₅₃Fill area, 1 wire (53 %) | 6.654 in²4293 mm² |
Same trade size, other conduit types
All Conduit Sizes sizes
Sources
- NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
- NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
- Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
- Steel Tube Institute: Intermediate metal conduit
- PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
- IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.