4" PVC Sch 40 Conduit Dimensions & Fill

Conduit Sizes · PVC Schedule 40

4" PVC Sch 40 conduit has a nominal inside diameter of 3.998 in (101.5 mm) and a total inside area of 12.554 in² (8,099 mm²). NEC Chapter 9 allows 5.022 in² (3240 mm²) for three or more conductors (40 %), 3.892 in² (2511 mm²) for two and 6.654 in² (4293 mm²) for one.

IDInside diameter (nominal)
101.5 mm3.998 in3.998 in101.5 mm
ODOutside diameter
114.3 mm4.500 in4.500 in114.3 mm
A₄₀Fill area, over 2 wires (40 %)
3240 mm²5.022 in²5.022 in²3240 mm²

Drawing

40 % fill areaID ⌀101.5 mmID ⌀3.998 inOD ⌀114.3 mmOD ⌀4.500 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

4" PVC Sch 40 specifications

Metric designator103
ODOutside diameter4.500 in114.3 mm
IDInside diameter (nominal)3.998 in101.5 mm
ATotal inside area (100 %)12.554 in²8,099 mm²
A₄₀Fill area, over 2 wires (40 %)5.022 in²3240 mm²
A₃₁Fill area, 2 wires (31 %)3.892 in²2511 mm²
A₅₃Fill area, 1 wire (53 %)6.654 in²4293 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.