4" PVC Sch 80 Conduit Dimensions & Fill

Conduit Sizes · PVC Schedule 80

4" PVC Sch 80 conduit has a nominal inside diameter of 3.786 in (96.2 mm) and a total inside area of 11.258 in² (7,263 mm²). NEC Chapter 9 allows 4.503 in² (2905 mm²) for three or more conductors (40 %), 3.490 in² (2252 mm²) for two and 5.967 in² (3850 mm²) for one.

IDInside diameter (nominal)
96.2 mm3.786 in3.786 in96.2 mm
ODOutside diameter
114.3 mm4.500 in4.500 in114.3 mm
A₄₀Fill area, over 2 wires (40 %)
2905 mm²4.503 in²4.503 in²2905 mm²

Drawing

40 % fill areaID ⌀96.2 mmID ⌀3.786 inOD ⌀114.3 mmOD ⌀4.500 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

4" PVC Sch 80 specifications

Metric designator103
ODOutside diameter4.500 in114.3 mm
IDInside diameter (nominal)3.786 in96.2 mm
ATotal inside area (100 %)11.258 in²7,263 mm²
A₄₀Fill area, over 2 wires (40 %)4.503 in²2905 mm²
A₃₁Fill area, 2 wires (31 %)3.490 in²2252 mm²
A₅₃Fill area, 1 wire (53 %)5.967 in²3850 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data