1" PVC Sch 40 Conduit Dimensions & Fill
Conduit Sizes · PVC Schedule 40
1" PVC Sch 40 conduit has a nominal inside diameter of 1.029 in (26.1 mm) and a total inside area of 0.832 in² (537 mm²). NEC Chapter 9 allows 0.333 in² (215 mm²) for three or more conductors (40 %), 0.258 in² (166 mm²) for two and 0.441 in² (285 mm²) for one.
- IDInside diameter (nominal)
- 26.1 mm1.029 in1.029 in26.1 mm
- ODOutside diameter
- 33.4 mm1.315 in1.315 in33.4 mm
- A₄₀Fill area, over 2 wires (40 %)
- 215 mm²0.333 in²0.333 in²215 mm²
Drawing
1" PVC Sch 40 specifications
| Metric designator | 27 |
|---|---|
| ODOutside diameter | 1.315 in33.4 mm |
| IDInside diameter (nominal) | 1.029 in26.1 mm |
| ATotal inside area (100 %) | 0.832 in²537 mm² |
| A₄₀Fill area, over 2 wires (40 %) | 0.333 in²215 mm² |
| A₃₁Fill area, 2 wires (31 %) | 0.258 in²166 mm² |
| A₅₃Fill area, 1 wire (53 %) | 0.441 in²285 mm² |
Same trade size, other conduit types
All Conduit Sizes sizes
Sources
- NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
- NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
- Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
- Steel Tube Institute: Intermediate metal conduit
- PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
- IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads
Values last checked against these sources on November 15, 2026. · How we check data