1" PVC Sch 40 Conduit Dimensions & Fill

Conduit Sizes · PVC Schedule 40

1" PVC Sch 40 conduit has a nominal inside diameter of 1.029 in (26.1 mm) and a total inside area of 0.832 in² (537 mm²). NEC Chapter 9 allows 0.333 in² (215 mm²) for three or more conductors (40 %), 0.258 in² (166 mm²) for two and 0.441 in² (285 mm²) for one.

IDInside diameter (nominal)
26.1 mm1.029 in1.029 in26.1 mm
ODOutside diameter
33.4 mm1.315 in1.315 in33.4 mm
A₄₀Fill area, over 2 wires (40 %)
215 mm²0.333 in²0.333 in²215 mm²

Drawing

40 % fill areaID ⌀26.1 mmID ⌀1.029 inOD ⌀33.4 mmOD ⌀1.315 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

1" PVC Sch 40 specifications

Metric designator27
ODOutside diameter1.315 in33.4 mm
IDInside diameter (nominal)1.029 in26.1 mm
ATotal inside area (100 %)0.832 in²537 mm²
A₄₀Fill area, over 2 wires (40 %)0.333 in²215 mm²
A₃₁Fill area, 2 wires (31 %)0.258 in²166 mm²
A₅₃Fill area, 1 wire (53 %)0.441 in²285 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.