1" PVC Sch 80 Conduit Dimensions & Fill

Conduit Sizes · PVC Schedule 80

1" PVC Sch 80 conduit has a nominal inside diameter of 0.936 in (23.8 mm) and a total inside area of 0.688 in² (444 mm²). NEC Chapter 9 allows 0.275 in² (177 mm²) for three or more conductors (40 %), 0.213 in² (137 mm²) for two and 0.365 in² (235 mm²) for one.

IDInside diameter (nominal)
23.8 mm0.936 in0.936 in23.8 mm
ODOutside diameter
33.4 mm1.315 in1.315 in33.4 mm
A₄₀Fill area, over 2 wires (40 %)
177 mm²0.275 in²0.275 in²177 mm²

Drawing

40 % fill areaID ⌀23.8 mmID ⌀0.936 inOD ⌀33.4 mmOD ⌀1.315 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

1" PVC Sch 80 specifications

Metric designator27
ODOutside diameter1.315 in33.4 mm
IDInside diameter (nominal)0.936 in23.8 mm
ATotal inside area (100 %)0.688 in²444 mm²
A₄₀Fill area, over 2 wires (40 %)0.275 in²177 mm²
A₃₁Fill area, 2 wires (31 %)0.213 in²137 mm²
A₅₃Fill area, 1 wire (53 %)0.365 in²235 mm²

Schedule 80 PVC has the same OD as Schedule 40 but a thicker wall: 1" Sch 80 has 0.275 in² of 40 % fill area against 0.333 in² for Sch 40, about 17 % less.

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.