1" PVC Sch 80 Conduit Dimensions & Fill
Conduit Sizes · PVC Schedule 80
1" PVC Sch 80 conduit has a nominal inside diameter of 0.936 in (23.8 mm) and a total inside area of 0.688 in² (444 mm²). NEC Chapter 9 allows 0.275 in² (177 mm²) for three or more conductors (40 %), 0.213 in² (137 mm²) for two and 0.365 in² (235 mm²) for one.
- IDInside diameter (nominal)
- 23.8 mm0.936 in0.936 in23.8 mm
- ODOutside diameter
- 33.4 mm1.315 in1.315 in33.4 mm
- A₄₀Fill area, over 2 wires (40 %)
- 177 mm²0.275 in²0.275 in²177 mm²
Drawing
1" PVC Sch 80 specifications
| Metric designator | 27 |
|---|---|
| ODOutside diameter | 1.315 in33.4 mm |
| IDInside diameter (nominal) | 0.936 in23.8 mm |
| ATotal inside area (100 %) | 0.688 in²444 mm² |
| A₄₀Fill area, over 2 wires (40 %) | 0.275 in²177 mm² |
| A₃₁Fill area, 2 wires (31 %) | 0.213 in²137 mm² |
| A₅₃Fill area, 1 wire (53 %) | 0.365 in²235 mm² |
Schedule 80 PVC has the same OD as Schedule 40 but a thicker wall: 1" Sch 80 has 0.275 in² of 40 % fill area against 0.333 in² for Sch 40, about 17 % less.
Same trade size, other conduit types
All Conduit Sizes sizes
Sources
- NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
- NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
- Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
- Steel Tube Institute: Intermediate metal conduit
- PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
- IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.