1" IMC Conduit Dimensions & Fill

Conduit Sizes · IMC: intermediate metal conduit

1" IMC conduit has a nominal inside diameter of 1.105 in (28.1 mm) and a total inside area of 0.959 in² (619 mm²). NEC Chapter 9 allows 0.384 in² (248 mm²) for three or more conductors (40 %), 0.297 in² (192 mm²) for two and 0.508 in² (328 mm²) for one.

IDInside diameter (nominal)
28.1 mm1.105 in1.105 in28.1 mm
ODOutside diameter
32.8 mm1.290 in1.290 in32.8 mm
A₄₀Fill area, over 2 wires (40 %)
248 mm²0.384 in²0.384 in²248 mm²

Drawing

40 % fill areaID ⌀28.1 mmID ⌀1.105 inOD ⌀32.8 mmOD ⌀1.290 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

1" IMC specifications

Metric designator27
ODOutside diameter1.290 in32.8 mm
IDInside diameter (nominal)1.105 in28.1 mm
ATotal inside area (100 %)0.959 in²619 mm²
A₄₀Fill area, over 2 wires (40 %)0.384 in²248 mm²
A₃₁Fill area, 2 wires (31 %)0.297 in²192 mm²
A₅₃Fill area, 1 wire (53 %)0.508 in²328 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.