5" PVC Sch 80 Conduit Dimensions & Fill
Conduit Sizes · PVC Schedule 80
5" PVC Sch 80 conduit has a nominal inside diameter of 4.768 in (121.1 mm) and a total inside area of 17.855 in² (11,519 mm²). NEC Chapter 9 allows 7.142 in² (4608 mm²) for three or more conductors (40 %), 5.535 in² (3571 mm²) for two and 9.463 in² (6105 mm²) for one.
- IDInside diameter (nominal)
- 121.1 mm4.768 in4.768 in121.1 mm
- ODOutside diameter
- 141.3 mm5.563 in5.563 in141.3 mm
- A₄₀Fill area, over 2 wires (40 %)
- 4608 mm²7.142 in²7.142 in²4608 mm²
Drawing
5" PVC Sch 80 specifications
| Metric designator | 129 |
|---|---|
| ODOutside diameter | 5.563 in141.3 mm |
| IDInside diameter (nominal) | 4.768 in121.1 mm |
| ATotal inside area (100 %) | 17.855 in²11,519 mm² |
| A₄₀Fill area, over 2 wires (40 %) | 7.142 in²4608 mm² |
| A₃₁Fill area, 2 wires (31 %) | 5.535 in²3571 mm² |
| A₅₃Fill area, 1 wire (53 %) | 9.463 in²6105 mm² |
Same trade size, other conduit types
All Conduit Sizes sizes
Sources
- NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
- NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
- Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
- Steel Tube Institute: Intermediate metal conduit
- PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
- IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.