5" PVC Sch 80 Conduit Dimensions & Fill

Conduit Sizes · PVC Schedule 80

5" PVC Sch 80 conduit has a nominal inside diameter of 4.768 in (121.1 mm) and a total inside area of 17.855 in² (11,519 mm²). NEC Chapter 9 allows 7.142 in² (4608 mm²) for three or more conductors (40 %), 5.535 in² (3571 mm²) for two and 9.463 in² (6105 mm²) for one.

IDInside diameter (nominal)
121.1 mm4.768 in4.768 in121.1 mm
ODOutside diameter
141.3 mm5.563 in5.563 in141.3 mm
A₄₀Fill area, over 2 wires (40 %)
4608 mm²7.142 in²7.142 in²4608 mm²

Drawing

40 % fill areaID ⌀121.1 mmID ⌀4.768 inOD ⌀141.3 mmOD ⌀5.563 in
Dashed circle: same area as the 40 % fill allowance.Drawn to scale · Dimensions in mmDimensions in inches

5" PVC Sch 80 specifications

Metric designator129
ODOutside diameter5.563 in141.3 mm
IDInside diameter (nominal)4.768 in121.1 mm
ATotal inside area (100 %)17.855 in²11,519 mm²
A₄₀Fill area, over 2 wires (40 %)7.142 in²4608 mm²
A₃₁Fill area, 2 wires (31 %)5.535 in²3571 mm²
A₅₃Fill area, 1 wire (53 %)9.463 in²6105 mm²

Same trade size, other conduit types

All Conduit Sizes sizes

Compare all 80 conduit sizes in the Conduit Sizes chart →

Sources

  1. NFPA 70 (National Electrical Code), Chapter 9 Tables 1, 4 and 5
  2. NECA/IBEW: NEC Chapter 9 Table 4, Dimensions and percent area of conduit and tubing
  3. Wheatland Tube: EMT and conduit brochure (ANSI C80.1 / C80.3 / C80.6 dimensions)
  4. Steel Tube Institute: Intermediate metal conduit
  5. PDHonline E276: Conduit fill calculations (NEC Chapter 9 worked examples)
  6. IEC 61386-1 / EN 61386: Conduit systems for cable management; EN 60423: conduit outside diameters and threads

Values last checked against these sources on November 15, 2026. · How we check data

Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.