PEX Tubing Size Chart: OD, ID and Wall (CTS SDR 9 and Metric)
Dimensions of PEX tubing. US PEX is copper tube size (OD = nominal + 1/8 in), so 1/2-in PEX is 0.625 in (15.9 mm) OD; the SDR 9 wall leaves an ID of about 0.485 in, smaller than 1/2-in copper.
Size chartSort by any column, or filter to find a row
| Size | ODOutside diametermminmm · in | tWall thicknessmminmm · in | IDInside diametermminmm · in | SDR (OD ÷ wall) | Pressure rating at 73 °F (23 °C)barpsibar · psi | Pressure rating at 180 °F (82 °C)barpsibar · psi |
|---|---|---|---|---|---|---|
| US / Canada: CTS SDR 9 (ASTM F876/F877) | ||||||
| 1/4" PEX | 9.50.375 | 1.60.062 | 6.40.251 | — | 11.0160 | 6.9100 |
| 3/8" PEX | 12.70.500 | 1.80.070 | 9.10.360 | — | 11.0160 | 6.9100 |
| 1/2" PEX | 15.90.625 | 1.80.070 | 12.30.485 | 9 | 11.0160 | 6.9100 |
| 5/8" PEX | 19.10.750 | 2.10.083 | 14.80.584 | 9 | 11.0160 | 6.9100 |
| 3/4" PEX | 22.20.875 | 2.50.097 | 17.30.681 | 9 | 11.0160 | 6.9100 |
| 1" PEX | 28.61.125 | 3.20.125 | 22.20.875 | 9 | 11.0160 | 6.9100 |
| 1-1/4" PEX | 34.91.375 | 3.90.153 | 27.21.069 | 9 | 11.0160 | 6.9100 |
| 1-1/2" PEX | 41.31.625 | 4.60.181 | 32.11.263 | 9 | 11.0160 | 6.9100 |
| 2" PEX | 542.125 | 60.236 | 421.653 | 9 | 11.0160 | 6.9100 |
| Metric PE-X (EN ISO 15875) | ||||||
| 16 × 2.0 mm | 160.630 | 20.079 | 120.472 | 8 | — | — |
| 16 × 2.2 mm | 160.630 | 2.20.087 | 11.60.457 | 7.3 | — | — |
| 17 × 2.0 mm | 170.669 | 20.079 | 130.512 | 8.5 | — | — |
| 20 × 2.0 mm | 200.787 | 20.079 | 160.630 | 10 | — | — |
| 20 × 2.8 mm | 200.787 | 2.80.110 | 14.40.567 | 7.1 | — | — |
| 25 × 3.5 mm | 250.984 | 3.50.138 | 180.709 | 7.1 | — | — |
| 32 × 4.4 mm | 321.260 | 4.40.173 | 23.20.913 | 7.3 | — | — |
No exact match. The nearest sizes:
CTS, SDR and how PEX is named
US PEX uses CTS (copper tube size): the OD equals the OD of copper tube of the same nominal size, nominal + 1/8 in. So PEX fittings and copper-tube push fittings share the OD: 1/2 in = 0.625 in, 3/4 in = 0.875 in, 1 in = 1.125 in.
SDR 9 means the wall is one ninth of the OD, so every size has the same pressure rating: 160 psi at 73 °F, 100 psi at 180 °F (80 psi at 200 °F).
Metric PE-X is named OD × wall in mm: 16 × 2.0, 20 × 2.8. The SDR (or series S) follows from those two numbers; check the printed pressure class (e.g. 6 bar at 70 °C) for heating circuits.
About PEX Tubing Sizes
Flow: because of the thicker wall, 1/2-in PEX has about 0.485 in bore against 0.545 in for type L copper; designers often step up one size on long runs or use home-run manifolds with 3/8 or 1/2-in branches.
PEX-A, PEX-B and PEX-C are the same size and pressure class under ASTM F876; the letters are crosslinking methods. Fitting systems differ: expansion (F1960) fits PEX-A, crimp and clamp rings (F1807, F2159) fit all types.
Oxygen-barrier PEX (EVOH layer) is for closed heating loops with iron components; the barrier does not change the OD.
PEX-AL-PEX (ASTM F1282) and European multilayer pipe (16 × 2.0, 20 × 2.0, 26 × 3.0 mm) look similar but need their own fittings.
Questions
What is the OD of 1/2 inch PEX?
0.625 in (5/8 in, 15.9 mm). 3/4-in PEX is 0.875 in and 1-in PEX 1.125 in OD.
What is the inside diameter of 1/2 inch PEX?
About 0.485 in (12.3 mm) at the minimum 0.070-in wall; 3/4 in about 0.681 in; 1 in about 0.875 in.
What pressure is PEX rated for?
SDR 9 CTS PEX: 160 psi at 73 °F, 100 psi at 180 °F and 80 psi at 200 °F.
Is PEX the same size as copper?
Same OD as copper tube of the same nominal size (CTS), so push-fit fittings work on both; the PEX bore is smaller.
What does 16 x 2 PEX mean?
16 mm outside diameter with a 2.0 mm wall, giving a 12 mm bore. It is the standard underfloor heating size in Europe.
Sources
- ASTM F876: Standard Specification for Crosslinked Polyethylene (PEX) Tubing (Table 2, CTS dimensions)
- ASTM F877: Crosslinked Polyethylene (PEX) Hot- and Cold-Water Distribution Systems
- Plastics Pipe Institute: PEX design guide and TR-4 pressure ratings (160 psi @ 73 °F, 100 psi @ 180 °F)
- EN ISO 15875-2: Plastics piping systems for hot and cold water installations, crosslinked polyethylene (PE-X), Part 2 Pipes
Values last checked against these sources on November 15, 2026. · How we check data
Reference values for planning and identification. Confirm critical dimensions with the manufacturer's drawing or the current edition of the standard before production.